page 16 — DCa150USJ2 60 hz generator • operation anD partS manUal — rev. #0 (08/22/11) 
GENERATOR
This  MQ  Power  generator  (Figure  3)  is  a  high  quality 
portable (requires a trailer for transport) power source for 
telecom sites, lighting facilities, power tools, submersible 
pumps and other industrial and construction machinery.
engine operating panel
The “Engine Operating Panel” is provided with the following:
 
„
Tachometer
 
„
Water Temperature Gauge
 
„
Oil Pressure Gauge
 
„
Charging Ammeter Gauge
 
„
Fuel Level Gauge
 
„
Panel Light/Panel Light Switch
 
„
ECU Controller
 
„
Engine Speed Switch
 
„
Emergency Stop Button
 
„
Emergency Stop Lamp
 
„
Warning Lamp
 
„
Pre-Heat Lamp
 
„
Fuel Leak Detected Alarm Lamp
 
„
Diagnostic Gauge
generator Control panel
The “Generator Control Panel” is provided with the following:
 
„
Frequency Meter (Hz)
 
„
AC Ammeter (Amps)
 
„
AC Voltmeter (Volts)
 
„
Ammeter Change-Over Switch
 
„
Voltmeter Change-Over Switch
 
„
Voltage Regulator
 
„
3-Pole, 400 amp Main Circuit Breaker
 
„
“Control Box” (located behind the Gen. Control Panel)
• Automatic Voltage Regulator
• Current Transformer
• Over-Current Relay
• Starter Relay
• Voltage Selector Switch
oUtpUt terminal panel
The “Output Terminal Panel” is provided with the following:
 
„
Three 120/240V output receptacles (CS-6369), 50A
 
„
Three auxiliary circuit breakers, 50A
 
„
Two 120V output receptacles (GFCI), 20A
 
„
Two GFCI circuit breakers, 20A
 
„
Five output terminal lugs (3Ø power)
open Delta exCitation SYStem
This generator is equipped with the state of the art 
“open-
Delta” excitation system. The open delta system consist 
of  an  electrically  independent  winding  wound  among 
stationary windings of the AC output section.
There are four connections of the open delta A, B, C and 
D. During steady state loads, the power from the voltage 
regulator is supplied from the parallel connections of A to 
B, A to D, and C to D. These three phases of the voltage 
input to the voltage regulator are then rectified and are the 
excitation current for the exciter section. 
When a heavy load, such as a motor starting or a short 
circuit  occurs,  the  automatic  voltage  regulator  (AVR) 
switches the configuration of the open delta to the series 
connection of B to C. This has the effect of adding the 
voltages of each phase to provide higher excitation to the 
exciter section and thus better voltage response during the 
application of heavy loads. 
The connections of the AVR to the AC output windings are 
for sensing only. No power is required from these windings.
The open-delta design provides virtually unlimited excitation 
current, offering maximum motor starting capabilities. The 
excitation does not have a 
“fixed ceiling” and responds 
according the demands of the required load.
engine
This generator unit incorporates an John Deere 6068HF285 
diesel  engine. This  engine  is  designed  to  meet  every 
performance  requirement  for  the  generator.  Reference 
Table 2 for engine specifications. 
In keeping with MQ Power’s policy of constantly improving 
its products, the specifications quoted herein are subject 
to change without prior notice.
eleCtriC governor SYStem
The electric governor system controls the RPMs of the engine.  
When  the  engine  demand  increases  or  decreases,  the 
governor system regulates the frequency variation to ±.25%. 
extenSion CaBleS
When electric power is to be provided to various tools or 
loads at some distance from the generator, extension cords 
are  normally  used.  Cables  should  be  sized  to  allow  for 
distance in length and amperage so that the voltage drop 
between the generator and point of use (load) is held  to 
a minimum. Use the cable selection chart (Table 6) as a 
guide for selecting proper extension cable size.