DCa150USJ2 60 hz generator • operation anD partS manUal — rev. #0 (08/22/11) — page 35
generatOr cOntrOl panel
Figure 5. Generator Control Panel
OFF
W
U
V
OFF
W-U
V-W
U-V
DECREASE
INCREASE
1
AUTO
MANUAL
OFF/RESET
LOW OIL PRESSURE
HIGH COOLANT TEMPERATURE
OVERCRANK
OVERSPEED
ENGINE RUNNING
MOOOOO-20001Q
2
3
4
6
7
5
The definitions below describe the controls and functions 
of the Generator Control Panel (Figure 5).
1. 
main Circuit Breaker—This three-pole, 400A main 
breaker  is  provided  to  protect  the  the  U,V,  and W 
Output Terminal Lugs from overload.
2. 
voltage regulator Control — Allows ±15% manual 
adjustment of the generator’s output voltage.
3. 
ammeter Change-over Switch — This switch allows 
the AC ammeter to indicate the current flowing to the 
load connected to any phase of the output terminals, 
or to be switched off. This switch does not effect the 
generator output in any fashion, it is for current reading 
only.
4. 
voltmeter Change-over Switch — This switch allows 
the AC voltmeter to indicate phase to phase voltage 
between any two phases of the output terminals or to 
be switched off.
5. 
Frequency meter — Indicates the output frequency 
in hertz (Hz). Normally 60 Hz.
6. 
AC Ammeter — Indicates the amount of current the 
load is drawing from the generator per leg selected by 
the ammeter phase-selector switch.
7. 
aC voltmeter — Indicates the output voltage present 
at the U,V, and W Output Terminal Lugs.
Located behind the generator control panel is the Generator 
Control  Box. This  box  contains  some  of  the  necessary 
electronic  components  required  to  make  the  generator 
function.
The  Control  Box  is  equipped  with  the  following  major 
components:
 
„
Over-Current Relay
 
„
Automatic Voltage Regulator (AVR)
 
„
Starter Relay
 
„
Current Transformer
 
„
Voltage Selector Switch
 
„
Main Circuit Breaker
 NOTICE
Remember the
 overcurrent relay monitors the current 
flowing from the 
U,v, and W output terminal lugs 
to the load.
In the event of a short circuit or over current condition, 
it will automatically trip the 400 amp main breaker.
To restore power to the 
Output Terminal Panel, press 
the reset button on the overcurrent relay and place the 
main circuit breaker in the closed position (ON).