Crestron cen-io User Manual

Page of 36
Ethernet Input/Output Module 
Crestron CEN-IO
 
SNMP Configuration 
Depressing “2” from the NETWORK FUNCTIONS MENU opens the SNMP 
CONFIGURATION MENU which appears on the screen as four options.  
SNMP CONFIGURATION MENU in Viewport Window 
 
Configure NMS (Network Management Station) Trap catchers 
Depressing “1” from the SNMP CONFIGURATION MENU opens the 
CONFIGURE NMS TRAP CATCHERS MENU which appears on the screen as 
four options. A NMS trap catcher is an NMS configured to receive the traps 
originating from the CEN-IO.  
CONFIGURE NMS TRAP CATCHERS MENU in Viewport Window 
 
•  Display NMS Trap Catchers - Depressing “1” from the CONFIGURE 
NMS TRAP CATCHERS MENU instructs the program to reveal its 
three trap catchers. Once displayed, the program prompts the user to 
‘Press any key to continue’. Doing so displays the CONFIGURE NMS 
TRAP CATCHERS MENU again.  
•  Add NMS Trap catcher - Depressing “2” from the CONFIGURE NMS 
TRAP CATCHERS MENU permits the user to add a new trap catcher. 
The program prompts the user to enter the trap catcher address. Enter 
the address (#.#.#.#) and depress ENTER. The program responds by 
repeating the new address and prompting the user to ‘Press any key to 
continue’. Doing so displays the CONFIGURE NMS TRAP 
CATCHERS MENU again. The newly added address overwrites the 
first available address (0.0.0.0). If there are no addresses available, the 
program responds with the message: ‘All three addresses are filled, 
remove one before adding’.  
•  Remove NMS Trap catcher - Depressing “3” from the CONFIGURE 
NMS TRAP CATCHERS MENU permits the user to delete an existing 
trap catcher. The program lists addresses for each trap catcher and 
prompts the user to ‘Enter the entry number to remove’. Enter the entry 
number (1, 2, or 3). The program responds by prompting the user to 
‘Press any key to continue’. Doing so displays the CONFIGURE NMS 
TRAP CATCHERS MENU again.  
10  
  Ethernet Input/Output Module: CEN-IO 
Operations Guide - DOC. 5718