FIELD CONTROLS 46477000 User Manual

Page of 4
DRAFT INDUCER KIT WITH CONTROL KIT  
Model: DI PAK MV & DI PAK MVFG 
(NOTE:  DI PAK MVFG units are designed for the Flame Guard units built 
by American Water Heater.  All other manufacturers use DI PAK MV
This draft inducer kit is designed for installation onto vent systems serving 
30 millivolt standing pilot gas fired water heaters with gas valves having a 
manifold pressure tap port (1/8 FPT) 
NOTE:  DI-1 Model must be used on 4” diameter vent pipe. 
I
TEMS INCLUDED IN KIT
 
1) DI-1,2 or 3 Draft Inducer with pre-attached power cable 
1) Fan control gas pressure switch with built in post purge option and pre-wired power cord 
1) 1/8" NPT x 3 inch pipe nipple 
1) 1/8" NPT pipe tee 
1) TCA-1 Thermocouple Adapter (DI PAK MV) 
1) TCA-2 Left Handed Thermocouple Adapter (DI PAK MVFG) 
1) 6 ft. length of 12-2 wire 
1) 12 inch jumper wire 
1) Flexible conduit connector 
2) GSK-3 Spillage Switch 
DO NOT DESTROY 
THESE INSTRUCTIONS MUST REMAIN WITH EQUIPMENT 
CAUTION:  Draft inducers are designed to increase draft in venting applications where inadequate natural draft exists. 
This device is NOT designed for sidewall venting applications. The vent to which the inducer is to be mounted is to be 
installed in accordance with NFPA 54, NFPA 31, or other local codes.   
This device MUST be installed by a qualified installer in accordance with the manufacturers installation instructions. 
Appliances should have a maximum measure flue gas temperature of 750°F at the desired location of the draft inducer. 
“Qualified Installer” shall mean an individual who has been properly trained or a licensed installer. The installer MUST 
write or imprint his name, phone number, and date of installation on the tag provided with this device. The tag MUST be 
attached to the draft inducer. Recording burner and draft inducer operation information (draft level, efficiency, etc) is 
recommended as a guide for future service.