6.6.2 Messages 
list 
 
 
Code 
Message 
Meaning 
4002 
WATCHDOG 
RESET 
The microprocessor has detected an incorrect operation: 
Transfers the Load on Utility and performs a program reset. 
The  Inverter will restart automatically and will supply the 
Load. 
4111 
RECTIFIER 
UTILITY OK 
Rectifier Input Utility is again within the admitted tolerance 
(voltage, frequency and phase). 
4119 
BATTERY TEST 
STARTED 
Start of Manual or Automatic Battery Test
4120 
BATTERY TEST 
STOPPED 
End of Manual or Automatic Battery Test
4161 
RECTIFIER 
ON 
Rectifier started. 
4162 
RECTIFIER 
OFF 
Rectifier shutdown. 
4163 
GENERATOR 
ON 
Customer Interface (X1 - 11, 22) received a Gen-set ON 
signal. 
Operating mode depend on setting of Parameters. 
4164 
GENERATOR 
OFF 
Customer Interface (X1 - 11, 22) received a Gen-set OFF 
signal. 
Function Bypass enabled depends on setting of Parameter. 
4302 
INVERTER 
CANNOT BE 
TURNED ON 
Inverter cannot be switched on because one of the following 
conditions is still present: 
• 
Over Temperature 
• 
Low Battery Voltage 
• 
Inverter Fuses 
• 
Overload 
• 
K7 opening Failure 
• 
High Battery Voltage 
• 
DC Low 
• 
EPO 
4303 
INVERTER 
CANNOT BE 
TURNED OFF 
Inverter cannot be switched OFF, because the Load cannot 
be switched to Utility (voltage out of tolerance, not synchrony, 
BP blocked). 
4361 
INVERTER 
ON 
The command to start the Inverter has been activated on the 
control panel. 
4362 
INVERTER 
OFF 
The command to switch OFF the Inverter has been activated 
by the control panel or automatically for alarm presence. 
4411 
BYPASS UTILITY 
OK 
Bypass Input Utility is again within tolerance (voltage, 
frequency and phase). 
4500 
COMMAND 
LOAD OFF 
Disconnection of the Load by opening K6 and K7 for: 
EPO / total off / Overload / stop operation
4521 
NO BYPASS 
POWER 
With the Load supplied by Automatic Bypass, a Utility Failure 
or K6 opening occurred. 
4534 
MULTIPLE LOAD 
TRANSFER 
2 transfers Inverter- Utility have been detected in a short time, 
(default 30 sec.).