3.7.3  Battery over current protection and wire sizing 
• 
Please read the safety precautions at the front of this guide carefully, and thoroughly 
review the Battery manufacturers installation and maintenance manual before connecting 
the batteries to the UPS. 
• 
If the UPS system has been purchased with an accompanying Battery Cabinet, that 
cabinet should have an integral Battery Circuit Breaker
If the UPS has been purchased without a Battery Cabinet or remote rack mounted 
batteries are to be used then DC over current protection must be provided by others. 
• 
Choose an appropriate DC fuse or circuit breaker using the current data in the chart 
below. 
• 
Minimum Battery Cable requirement is based on the current data below. 
 
The AC values below are current ratings per phase. 
These maximum and nominal ratings should be considered when choosing the 
appropriate AC over current protection device. 
NEC (National Electric Code) Section 210-20 a rules must be applied. 
DC current rating is the maximum battery discharge current which the UPS allows. 
(See Fig. 3.7.1-1 and 3.7.1.2) 
AC Input 
Rectifier 
AC Input 
Bypass 
AC Input 
DC Input 
F1 
F3 
 
Nom. Max. 
F2 
Nom. Max. 
F4 
SG Series 225 kVA 
301 A 
360 A 
271 A 
301 A 
360 A 
401 A 
SG Series 300 kVA 
401 A 
480 A 
361 A 
401 A 
480 A 
535 A 
 
Size of Branch Circuit Over current Protection - All Models: - "CAUTION - To reduce 
the risk of fire, only connect UPS to a circuit provided with (See below) maximum 
amperes branch circuit over current protection in accordance 
with the NEC (National Electric Code), NSI / NFPA 70 
AC Input 
Rectifier 
AC Input 
Bypass 
AC Input 
DC Input 
 
F1 
F2 
F3 
F4 
SG Series 225 kVA 
450 A
 
350 A
 
450 A
 
600 A
 
SG Series 300 kVA 
600 A
 
500 A
 
600 A
 
700 A
 
 
 
WIRING 
Wire sizing according to 
NEC Section 210-20 (a)     Table 310-16 
Use 75°C (167°C) copper wire
 
 
Wiring requirements: 
AC INPUT RECTIFIER: 
3-Phase, 3 wire plus Ground 
AC INPUT BYPASS: 
3-Phase, 4 wire plus Ground 
AC OUTPUT: 
3-Phase, 4 wire plus Ground 
DC INPUT: 
2 wire (positive and negative) plus Ground
 
 
Maximum cable diameter that compression lugs can accept. 
Refer to torque specifications table for torque requirements. 
 
Rectifier Input Bypass Input
DC Input 
AC Output 
GND 
SG Series 225 kVA 
2 x 500 kcmil  2 x 500 kcmil  2 x 750 kcmil  2 x 500 kcmil 
350 kcmil 
SG Series 300 kVA 
2 x 750 kcmil  2 x 500 kcmil  2 x 750 kcmil  2 x 500 kcmil 
350 kcmil