Certified for US EPA-Tier 2 / Constant Speed
Standard Model [1250kWe/60Hz]
MITSUBISHI
S12R-Y2PTAW-1
          SPECIFICATION SHEET
DIESEL ENGINES
FUEL SYSTEM
Fuel Injector
          Mitsubishi PS6 Type × 2 
Maximum Suction Head of Feed Pump - mm Hg (in. Hg)
75
(3.0)
Maximum Static Head of Return Pipe - mm Hg (in.Hg)
150
(5.9)
STARTING SYSTEM
Battery Charging Alternator - V- Ah
24-30
Starting Motor Capacity - V - kW
24-7.5 × 2
Maximum Allowable Resistance of Cranking Circuit - m Ω
1.5
Recommended Minimum Battery Capacity
At 5
o
C (41
o
F) and above - Ah
300
Below 5
o
C (41
o
F) through - 5
o
C (23
o
F)
600
The specifications are subject to change without notice.
APPLICATION : GENERATOR
Pub. No. T13-0634-E