V4055A,B,D,E ON-OFF FLUID POWER GAS VALVE ACTUATOR
60-2309—1
3
2
ORDERING INFORMATION
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the 
TRADELINE® Catalog or price sheets for complete ordering number.
If you have additional questions, need further information, or would like to comment on our products or services, please write or 
phone:
1. Your local Honeywell Automation and Control Products Sales Office (check white pages of your phone directory).
2. Honeywell Customer Care
1885 Douglas Drive North
Minneapolis, Minnesota 55422-4386
In Canada—Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Toronto, Ontario M1V 4Z9.
International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France, 
Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.
SPECIFICATIONS
Models:
V4055A Actuator, with V5055, V5097 or VE5000 Gas Valves, 
provides on-off control of fuel. With proper adapter (see 
Accessories), it replaces the V4034 Actuator on a V5034 
Gas Valve.
V4055B Actuator is a high pressure version of V4055A.
V4055D Actuator is identical to V4055A, except has a 
Proof-of-Closure Switch. Used with V5055C/V5097C 
(double seal) for valve seal overtravel interlock.
V4055E Actuator is identical to V4055B, except has a 
Proof-of-Closure Switch. Used with V5055E/V5097E 
(double seal) for valve seal overtravel interlock.
NEMA 4 weatherproof models available.
Nominal Opening Time: See Table 1.
Table 1. Nominal Opening Time (seconds).
Maximum Closing Time: One second when de-energized.
Ambient Operating Temperature Ratings:
60 Hz Models: -40°F to +150°F (-40°C to +66°C).
50 Hz, 50/60 Hz Models: -10°F to +158°F (-23°C to +70°C).
Mounting: V4055 Actuator attaches directly to V5055/V5097 
Valve with two sets of screws positioned 90 degrees apart. 
Combination is multipoise.
NOTE: 220 to 240 Vac, 50/60 Hz models are vertical 
mount only.
Pressure Ratings: See Table 2.
Table 2. Pressure Ratings of Valve-Actuator Combinations.
a
 Max Operating Pressure Differential (UL) or Max Operating Pressure (CSA): maximum allowable pressure drop from inlet to 
outlet for proper operation .
b
 Max rated pressure (UL) or Max Close-off Pressure (CSA) : maximum pressure that the valve can be exposed to without leak-
age or damage to the valve.
c
 Applies for small-body V5097 valves 3/4” up to 2” pipe size.
d
 Applies for large-body V5097 valves 2” up to 3” pipe size.
e
 V5055A, B, C only.
Electrical Ratings: See Tables 3 and 4.
Model
50 Hz
60 Hz
Standard
32
26
Fast-opening
16
13
Model
Pipe Size
STANDARD PRESSURE ACTUATORS 
V4O55A, D, F, G
HIGH PRESSURE ACTUATORS 
V4O55B, E
M.O.P.D.
a
 
Max. Rated 
Pressure
b
 
M.O.P.D.
a
 
Max. Rated 
Pressure 
b
 
STANDARD 
PRESSURE VALVES 
V5055A, B, C, F, 
V5097A, B, C
3/4” to 1-1/2”
c
5 PSI
340 mbar 15 PSI
1.0 Bar
15 PSI
1030 mbar 15 PSI
1.0 Bar
2” to 3”
d
5 PSI
340 mbar 15 PSI
1.0 Bar
15 PSI
1030 mbar 15 PSI
1.0 Bar
4” flanged
e
3 PSI
207 mbar 15 PSI
1.0 Bar
5 PSI
340 mbar
15 PSI
1.0 Bar
HIGH PRESSURE 
VALVES V5055D, E, 
V5097D, E
3/4” to 1-1/2”
c
5 PSI
340 mbar 75 PSI
5.0 Bar
25 PSI
1720 mbar 75 PSI
5.0 Bar
2” to 3”
d
5 PSI
340 mbar 45 PSI
3.0 Bar
15 PSI
1030 mbar 45 PSI
3.0 Bar