Honeywell 63-4526-01 User Manual

Page of 36
PIR APPLICATION GUIDE FOR TB7200 AND TB7300 SERIES THERMOSTATS
63-4526—01
18
11.
 
TB7300 stand-alone fan coil application—3 levels of occupancy with dual PIR sensors
Sequence of operation: 
At initial power-up, when the thermostat 24 Vac power supply is applied; the initial occupancy of the zone will be stand-by mode if 
the PIR devices do not detect any movement.
As soon as any of the PIR devices detect a movement or motion, the occupancy status switches to occupied and the occupied 
setpoints are used.
Anytime local motion is detected by one of the PIR devices, the elapsed stand-by timer value will be reset. If either PIR devices in 
the zone detect no motion for the entire stand-by timer duration, then the room switches to stand-by mode and the stand-by 
setpoints are used.
While in stand-by mode, if no motion is detected in the zone by either PIR device for the entire unoccupied timer duration, then 
the room switches to unoccupied mode and the unoccupied setpoints are used.
At anytime, if one of the PIR devices detects a local movement or motion, the occupancy status switches to occupied and the 
occupied setpoints are used.
Set-up and Configuration
Thermostat used
TB73x0X5014 (commercial models)
PIR used
BI1 configured for remote PIR sensor and 
TB-PIR-FCU-C cover
BI2 Configuration
None, no function
Stand-by timer value
2.0 hours
Unoccupied timer value 
6.0 hours
Network interface used
None, stand-alone
Remote PIR Sensor
 
Remote PIR Sensor
 
Unoccupied Time
= 6 Hours
Stand-By Time
 
= 2 Hours
 
First Movement Detected
 
by a PIR Device
 
Occupied
 
Stand-By
 
Unoccupîed
 
Time
Stand-By Time Elapsed
= Stand-By Mode
Unoccupied Time Elapsed
 
= Unoccupied Mode
 
Initial State at
 
Power-Up = Stand-By