Heat Controller TGC042C-3K-120 User Manual

Page of 35
 NOMINAL 5 TONS   
 
Model  
TGC060C-1K-135
TGC060C-3K-135
TGC060C-4K-135
 
Cooling Performance
Gross Cooling Capacity Btuh
60000
60000
60000
EER/SEER
11.6/13
11.6/13
11.6/13
Nominal CFM/ARI Rated CFM  
2000/1900
2000/1900
2000/1900
ARI Net Cooling Capacity Btuh  
58000
58000
58000
Net Sensible Capacity Btuh 
42000
42000
42000
Net Latent Capacity Btuh
16000
16000
16000
Net System Power kW 
5
5
5
 
Heating Performance (Package Gas/Electric)
3  
Heating Input Btuh 
135000
135000
135000
Heating Output Btuh
106500
109400
109400
Temperature Rise ºF
40-70
40-70
40-70
AFUE (%)
80
80
80
Steady State Efficiency (%)
81
81
81
Qty of Burners
6
6
6
Qty of Stages
1
1
1
Gas Connection Pipe Size, in. 
.5
.5
.5
 
Compressor 
Qty/Type  
 
Outdoor Sound Rating (dB)  
83
78
78
 
Outdoor Coil—Fin Type 
Tube Type 
Rifled
Rifled
Rifled
Tube Size in. OD 
0.375
0.375
0.375
Face Area sq. ft. 
16.56
16.56
16.56
Rows / Fins per inch  
2/22
2/22
2/22
 
Indoor Coil—Fin Type 
Tube Type 
Rifled
Rifled
Rifled
Tube Size in.
0.375
0.375
0.375
Face Area sq. ft.
5.17
5.17
5.17
Rows / Fins per inch 
3/15
3/15
3/15
Refrigerant Control 
TXV
TXV
TXV
Drain Connection Qty/Size, in. 
1/0.75
1/0.75
1/0.75
 
Outdoor Fan—Type 
Qty Used/Diameter in.  
1/24
1/24
1/24
Drive Type/Speeds 
Direct/1
Direct/1
Direct/1
CFM  
3930
3930
3930
Qty Motors-HP 
1-1/3
1-1/3
1-1/3
Motor RPM
1075
1075
1075
 
Indoor Fan—Type 
Qty Used/Diameter in.  
1/10x10
1/10x10
1/10x10
Drive Type/Speeds 
Direct/3
Direct/3
Belt/Variable
Motor Qty 
1
1
1
Motor HP 
1
1
3/4
Motor RPM 
1075
1075
1725
Motor Frame Size  
48
48
56
 
Filter—Type 
Furnished  
Yes
Yes
Yes
(Qty) Size Recommended in. 
(2)16x25x1
(2)16x25x1
(2)16x25x1
 
Refrigerant Charge Oz. 
160
160
160
 
Weights 
Net Weight lbs. 
597
597
597
Ship Weight lbs.  
604
604
604
Notes:
Forward Curved Centrifugal
Disposable
1/Copeland Scroll
Louvered
Corrugated
Propeller
1. Cooling performance is rated at 95ºF ambient, 80ºF/67ºF entering dry bulb/wet bulb temperatures. Gross capacity does not include the effect of fan 
motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for operation to plus or minus 20% of nominal cfm.  Units 
are certified and rated per ARI Standard 210/240. 
2. EER/SEER are rated ARI condition and accordance with DOE test procedures. 
3. Heating performance limit settings and rating data were established and approved under laboratory test conditions using American National 
Standard Institute standards. Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, rating should be resuced 4% for each 
1000 feet above sea level. 
GENERAL DATA
10
              Heat Controller, Inc. 
                         -10-