heatcraft-refrigeration-p h-im-fl1a User Manual

Page of 24
8
Liquid Lines 
Liquid lines should be sized for a minimum pressure drop to 
prevent “flashing”. Flashing in the liquid lines would create 
additional pressure drop and poor expansion valve operation. 
If a system requires long liquid lines from the receiver to the 
evaporator or if the liquid has to rise vertically upward any 
distance, the losses should be calculated to determine whether 
or not a heat exchanger is required. The use of a suction 
to liquid heat exchanger may be used to subcool the liquid 
to prevent flashing. This method of subcooling will normally 
provide no more than 20
˚
F subcooling on high pressure 
systems. The amount of subcooling will depend on the design 
and size of the heat exchanger and on the operating suction 
and discharge pressures. An additional benefit from the use 
of the suction to liquid type heat exchanger is that it can 
help raise the superheat in the suction line to prevent liquid 
return to the compressor via the suction line. Generally, heat 
exchangers are not recommended on R-22 low temperature 
systems. However, they have proved necessary on short, 
well insulated suction line runs to provide superheat at the 
compressor.
Figure 6. Suction P-Traps.
Slope 1/4" 
per 10 ft. 
toward 
compressor
Suction Lines
NOTE:  If the suction line must rise to a point  
higher than the suction connection on the 
evaporator, a suction line trap at the outlet 
of the evaporator must be provided. 
Horizontal suction lines should slope away from the evaporator 
toward the compressor at the rate of 1/4 inch per 10 feet for 
good oil return. When multiple evaporators are connected in 
series using a common suction line, the branch suction lines 
must enter the top of the common suction line. 
For dual or multiple evaporator systems, the branch lines to 
each evaporator should be sized for the evaporator capacity. 
The main common line should be sized for the total system 
capacity.
Suction lines that are outside of refrigerated space must be 
insulated. See the Line Insulation section on page 11 for more 
information.
Suction Line Risers
Prefabricated wrought copper traps are available, or a trap can 
be made by using two street ells and one regular ell. The suction 
trap must be the same size as the suction line. For long vertical 
risers, additional traps may be necessary. Generally, one trap is 
recommended for each length of pipe (approximately 20 feet) to 
insure proper oil movement. See Figure 6 below for methods of 
constructing proper suction line P-traps.