EXCEL 10 W7753A UNIT VENTILATOR CONTROLLER
95-7520—02
10
NOTE: The node can be reset by switching the node to MANUAL and then switching to the normal operating mode 
(using DestManMode).
Also, the Excel 10 network variables, AlarmLogX, where X is 1 through 5, that store the last five alarms to occur in the 
controller, are available. These points can be viewed through XBS, XI584 or E-Vision.
Table 1. Excel 10 Alarms.
Name of alarm or error bit
Alarm type 
number
NO_ALARM
0
No alarms presently detected.
INPUT_NV_FAILURE
1
One or more NV inputs have failed while receiving an update within their 
specified FAILURE_DETECT_TIME.
NODE_DISABLED
2
The control algorithm stopped because the controller is in DISABLED_MODE, 
or FACTORY_TEST mode. The control is shut down and disabled until power is 
cycled or the node is reset. See NOTE 1 below.
SENSOR_FAILURE
3
One or more sensors have failed.
FROST_PROTECTION_ALARM 4
The space temperature is below the frost alarm limit 42.8
°
F (6
°
C) when the 
mode is FREEZE_PROTECT. The alarm condition remains until the 
temperature exceeds the alarm limit plus hysteresis.
INVALID_SET_POINT
5
One of the Setpoints is not in the valid range.
LOSS_OF_AIR_FLOW
6
The Fan Status DI indicates that there is no air flow when the node is 
commanding the fan to run. The control is shut down and disabled until power is 
cycled or the node is reset. The alarm is not issued until FanFailTime seconds 
have elapsed since the loss-of-flow condition was first reported.
DIRTY_FILTER
7
The pressure drop across the filter exceeds the limit and the filter requires 
maintenance. The control runs normally.
SMOKE_ALARM
8
The smoke detector has detected smoke and the node has entered an 
emergency state.
IAQ_OVERRIDE
9
The indoor air quality sensor has detected that the indoor air quality is poorer 
than the desired standard and additional outdoor air is being brought into the 
conditioned space.
LOW_LIM_ECON_CLOSE
10
The economizer has to close beyond the minimum position to prevent the 
discharge air temperature from going below the discharge temperature low 
limit.
DRIP_PAN_FULL
11
Drip pan maintenance is required. Cooling control is disabled. Fan continues to 
run.
FREEZE_STAT
12
Very Cold Temperature detected inside the Unit Ventilator Cabinet. Control 
closes OA Damper, and open heat valve.
OAQ_ALARM
13
The configured outdoor air quality sensor has detected CO or CO
2
 levels that 
exceeds OaQStPt (plus 30 ppm hysteresis). When there is an OAQ_ALARM, 
the economizer damper is closed.
RETURN_TO_NORMAL
128
Return to no alarm after being in an alarm condition. This code is added 
numerically to another alarm code to indicate that the alarm condition has 
returned to normal.
ALARM_NOTIFY_DISABLED
255
The alarm reporting was turned off by the nviManualMode. No more alarms are 
reported until nviManualMode turns on alarm reporting or upon application 
restart.