T7350 COMMERCIAL PROGRAMMABLE THERMOSTAT
23
63-4368
APPENDIX C - NETWORK ERROR REPORTING
Table 16. 
Reporting T
7350H Errors.
T
7350H errors are reported through the manufacturer defined output network variable, nvoError. 
nvoError Field
Description
errLoclSpaceSensr
Local space temperature sensor not working.
0: Sensor value is OK. (power up value)
1: Sensor is configured to function and is out of range or disconnected.
errRemtSpaceSensr
Remote space temperature sensor not working.
0: Sensor value is OK. (power up value)
1: Sensor is configured to function and is out of range or disconnected.
errNetSpaceSensr
Network space temperature sensor not working.
0: Sensor value is OK. (power up value)
1: Sensor is configured by the thermostat to function but is not being updated by either the bound 
network sensor or by the subbase (faulty subbase). 
errLoclHumSensr
Local Humidity sensor not working.
0: Sensor value is OK. (power up value)
1: Sensor is configured to function and is out of range or disconnected.
errRemtHumSensr
Remote Humidity sensor not working.
0: Sensor value is OK. (power up value)
1: Sensor is configured to function and is out of range or disconnected.
errNetHumSensr
Network Humidity sensor not working.
0: Sensor value is OK. (power up value)
1: Sensor is configured by the thermostat to function but is not being updated by either the bound 
network sensor or by the subbase (faulty subbase).
errRemtOdSensr
Remote Outdoor air sensor not working.
0: Sensor value is OK. (power up value)
1: Sensor is configured to function and is out of range or disconnected.
errNetOdSensr
Network Outdoor air sensor not working.
0: Sensor value is OK. (power up value)
1: Sensor is configured by the thermostat to function but is not being updated by either the bound 
network sensor or by the subbase (faulty subbase).
errRemtSetPt
Remote wall module set point is out of range or disconnected.
0: Value is OK. (power up value)
1: Remote wall module set point is configured to function and is out of range or disconnected.
errDischSensr
Discharge sensor out of range or disconnected.
0: Sensor value is OK. (power up value)
1: Sensor is configured to function and is out of range or disconnected.
errIOConfig
Output configuration error. Considers sub-base type, heat pump / conventional application. 
maxCoolStgs, maxHeatStgs.
0: The outputs configuration is consistent with the sub-base type selected (power up value)
1: The number of outputs configured exceeds the capability of the sub-base to support them. 
errSubBaseType
Sub-base type error. 
0: The sub-base is a valid sub-base type (power up value)
1: The detected sub-base type is not supported by the firmware version of the cover assembly.
errUnused1
Not currently used
errSelfTest
Self test failure. Upon factory test power up, a self test of memory is performed. If external RAM, 
EEPROM, or application FLASH memory fails the test, nvoError.errSelfTest is set. This bit is intended 
for use in production testing. Field devices should ignore this bit.
0: Passed the test
1: Failed the test
errCoverCommFail
Communications between the cover and sub-base
0: No error (power up value)
1: The communications between the thermostat cover assembly and the sub-base has failed in 
one or both directions. The data from the cover to the sub-base has not been received for at least 
90 seconds, or data from the sub-base is not updating the cover assembly.