The temperature units are factory-set as degrees Celsius or
degrees Fahrenheit, as specified when the unit was ordered.
When the chiller is on, the indicator lights to the right of the
Actual temperature display on the control panel will show
which temperature unit  has been set.
To change this setting, move Dip Switch 1 on the control 
circuit board.
Disconnect and lock out main power
to the
chiller.
Open the electrical enclosure.
Change  Dip Switch 1 to:
OFF for °F
ON for °C
Close the electrical enclosure
and restore main
power to begin operating.
1
2
3
4
5
6
7
8
1
2
3
1
2
3
4
5
6
7
8
4
I
NSTALLATION
3-9
WARNING: Electric shock hazard
This equipment is powered by high voltage. Always
disconnect and lock out the main power source
before opening the unit or the electrical enclosure to
modify factory settings. Failure to disconnect and
lock out the main power source can result in severe
personal injury.