Crestron clti-2dim8 clxi-2dim8 User Manual

Page of 4
Crestron CLTI- & CLXI-2DIM8   
Terminal Block & Module 
Module Installation 
NOTE:  Before the bypass jumpers are removed, the 
Crestron Professional Automation Computer (PAC2), 
which provides control to the system, should be 
properly connected and contain a valid program to 
provide control of the module.  
CAUTION:  Module contains electrostatic sensitive 
devices (ESDs); unit must be handled from metal 
chassis – do not touch PC board or components. 
NOTE:  Modules are to be installed after enclosure 
has been completely wired. Refer to the terminal 
block installation procedure on page 2 for details.  
Wiring Diagram of the Terminal Block to the Module 
(Single-wide and Left Side Double-wide Enclosures) 
ENLARGEMENT DETAIL:
BYPASS JUMPERS ON 
RED AND BROWN 
SECTIONS HAVE BEEN 
REMOVED AFTER 
LOOSENING ALL 
SCREWS.
JUMPERS ON BLUE 
SECTIONS ARE NOT 
REMOVED.
JUMPERS INSTALLED
BYPASS
JUMPERS 
REMOVED
BLUE
 TO LOADS
BROWN FROM BREAKER
RED
 TO LOADS
RED
 TO LOADS
BROWN FROM BREAKER
BLUE FROM BREAKER PANEL
BLUE
 TO LOADS
BLUE FROM BREAKER PANEL
 
1.  Use the four supplied self-tapping pan Phillips 
screws (8B x ¼-inch (6 mm) length) to secure 
the module to the enclosure. 
2.  As shown in the wiring diagrams (next column), 
connect the wires from the module to the 
terminal block. Each wire exits the module 
directly in line with, and is the same color as, the 
terminal to which it should be connected. Wires 
are pre-stripped to 12 mm. Tighten to 1 Nm. Do 
not over tighten. 
3.  If the module is being installed above another 
module within the enclosure, attach the supplied 
module interconnect cable between the two 
modules. The illustration below depicts the area 
within a double-wide enclosure where the 
corners of four modules meet.  
NOTE:  One wire on the module interconnect cable 
may be a different color from the rest. The color has 
no bearing on its orientation during installation.  
Wiring Diagram of the Terminal Block to the Module 
(Right Side Double-wide Enclosures) 
Use Module Interconnect Cable to Wire Module to Module  
MODULE
INTERCONNECT
CABLE ATTACHED
CONNECTION
NOT
MADE
 
BLUE FROM BREAKER PANEL
BROWN FROM BREAKER
BLUE
 TO LOADS
BLUE FROM BREAKER PANEL
RED
 TO LOADS
BROWN FROM BREAKER
RED
 TO LOADS
BLUE
 TO LOADS
BYPASS
JUMPERS 
REMOVED
ENLARGEMENT DETAIL:
BYPASS JUMPERS ON RED 
AND BROWN SECTIONS 
HAVE BEEN REMOVED 
AFTER LOOSENING ALL 
SCREWS.
JUMPERS ON BLUE 
SECTIONS ARE NOT 
REMOVED.
JUMPERS
INSTALLED
 
4.  Turn on the circuit breaker and verify that the 
green PWR LED on the module lights, the 
breaker does not trip, and power is delivered to 
the loads.  
5.  Turn off the circuit breaker and remove the 
bypass jumpers on the brown and red sections of 
the terminal block. The jumpers on the blue 
sections of the terminal block must remain 
installed. Refer to the figures in the next column 
for a close-up of the jumpers.  
Installation Guide – DOC. 6411 
Terminal Block & Module:  CLTI- & CLXI-2DIM8  
  3