Black Box 945 User Manual

Page of 28
18
WATLOW Series 945
How to Use Data Communications
Commands
Data.1
Respns
Information
Comments
C1
ACTUAL
Actual process value
Between R1L and R1H
IN
0
J T/C
1
K T/C
2
T T/C
3
N T/C
4
PT2 T/C
5
C T/C
6
Not Used
7
R T/C
8
S T/C
9
B T/C
10
RTD whole
11
RTD tenths
12
0-5V
13
4-20mA
MODE
1
Auto mode
Multiple modes are possible.
2
Manual mode
4
Configuration mode
8
Calibration mode
16
Alarm silence active
ERR
0
No error
Multiple errors are possible.
1
Open sensor
2
Reversed sensor
4
Ambient sensor
8
Configuration
16
EE Checksum
32
A/D underflow
64
A/D overflow
128
Not used
ER2
0
No error
Cleared when ER2 is read.
1
Transmit buffer overflow
Only 1 ER2 response is valid.
2
Receive buffer overflow
3
Framing error
4
Overrun error
5
Parity error
6
Talking out of turn
7
Invalid reply error
8
Noise error
16
Process input active
17
Local/remote is local
18
Local/remote is remote
19
Remote not enabled
20
Command not found
21
Parameter not found
22
Incomplete command line
23
Invalid character
24
Number of chars. overflow
25
Input out of limit
26
Read only command
27
Write allowed only
BTYP
0
T/C Only
1
T/C, RTD whole, process
2
T/C, RTD tenths, process
3
R, S, B T/C
MDL
Displays 945 X
X = software revision
RSP1
Remote SP
Remote set point setting
"?" Command
The "?" Command reads a specific value of the Series 945 parameter (Data.1).
Tables 5 and 6 provide the complete list of parameters you may use, plus re-
sponses.
Table 5 -
"?" Commands
and Responses.
These commands
are READ ONLY.