Fluke 1744 User Manual

Page of 73
 
Power Quality Logger 
 Using 
the 
Logger 
 
  
11 
Using the Logger 
This section explains how to operate the 1744/1743 Power Quality Logger. 
A typical logging session includes four steps: 
1.  Preparing the Logger for use with the PQ Log software. 
2.  Installing the Logger at the logging site. 
3.  Leaving the Logger to collect data for a period. 
4.  Downloading and evaluating the logged data. 
These steps are described in the following pages. 
Logging Jobs 
Logging jobs are defined using the PQ Log software, and transferred to the 
Logger over the RS232 cable. Each job contains the following information: 
  Logging function (P for Model 1743, and P or A for Model 1744) 
  Measuring period, defined by start and end times 
  Time activated, switch or immediate job 
  Input range 
  Nominal voltage, primary and secondary voltage for logging with 
voltage converters 
  Logging of phase-neutral wire or phase-phase  
  Memory model  
  Averaging period length  
  Logging time periods 
  Interharmonics and signaling voltages  
  Limit values for events 
  Memory model for events: circular (first-in/first-out, continuous), or 
linear (quit logging when logging period is finished) 
  Logging of current-neutral wire 
  Converter ratios for current and voltage if using potential transformers 
(PTs) and current transformers (CTs) at a medium-voltage network 
site