Fluke 1744 User Manual

Page of 73
 
Power Quality Logger 
 
Methods of Logging   
  
27 
Evaluating the Logged Data 
You’ll use PQ Log to evaluate the logged data. Data can be read out during 
logging as well as at the end. 
1.  Connect the Logger to line power. 
2.  Connect the RS232 interface cable to your PC’s serial port, then to the 
Logger. 
3.  Start the PQ Log software. 
4.  Use PQ Log to transfer the data from the Logger to the PC. 
5.  Once the data is transferred, remove the RS232 interface cable and 
operating power from the Logger. 
6.  Evaluate the data using PQ Log. 
For details, refer to the PQ Log manual. 
Methods of Logging 
The following section describes methods of logging using the 1744/1743 
Logger. 
Measuring Ranges 
The Logger has three input ranges for each of its two connection systems: Wye 
connection (3-phase, 4-wire) and Delta connection (3-phase, 3-wire).  
Table 6. Measuring Ranges 
Connection 
Nominal Voltages (Wye/Delta) Max. Input Voltage  
Wye/Delta 
69 V / 120 V 
115 V / 200 V 
230 V / 400 V 
480 V / 830 V 
Phase/Neutral 
3-phase 4 wire 
69 V ~, +20% 
115 V ~, +20% 
230 V ~, +20% 
480 V ~, +20% 
Phase/Phase 
3-phase 3 wire 
120 V ~, +20% 
200 V ~, +20% 
400 V ~, +20% 
830 V ~, +20%