Fluke 1744 User Manual

Page of 73
 
Power Quality Logger 
 
Methods of Logging   
  
35 
Calculation of THD in Measuring Function P 
THD – Measuring Function P 
Function P does not measure harmonic values. 
Voltages:
1
2
1
2
V
V
V
THDV
RMS
=
 
V
RMS
: RMS value of total signal 
V
1
: RMS value of the fundamental 
Currents: 
1
2
1
2
I
I
I
THDI
RMS
=
 
I
RMS
: RMS value of the total signal. 
I
1
: RMS value of the fundamental. 
Note 
THDI for currents < 5% of IE (measuring range) can have additional 
uncertainties, or can be suppressed. 
Harmonics up to 50th order are taken into account.  
Flicker 
Flicker is the visual impression of unsteadiness in a light source whose 
luminance or spectral distribution changes over time. Flicker is logged in 
accordance with the IEC 61000-4-15 standard. The short-term (st) flicker Pst
t
 
is logged over a default standard interval of 10 minutes, and is used to 
calculate the long-term (lt) flicker Plt (by taking the sliding average of 12 
short-term values). The interval value can be changed as needed in PQ Log.