Intermatic 158ts10990 User Manual

Page of 1
MODEL: T7402B
SEVEN-DAY DIAL TIME SWITCH WITH
SPRING WOUND CARRY-OVER MOTOR
4 POLE SINGLE THROW
MINIMUM “ON” TIME 3-1/2 HR. UP TO 3-1/2 DAILY ON-OFF OPERATIONS
40 AMP. RESISTIVE EACH POLE 120V- 480V AC.
40 AMP. INDUCTIVE, TUNGSTEN EACH POLE 120V, 208V, 240V, OR
277V AC. 1000 VA PILOT DUTY EACH POLE 120V - 277V AC.
24 FLA, 144 LRA (2 HP) - 120V AC.; 28 FLA, 168 LRA (5 HP) - 240V AC.
SINGLE PHASE
28 FLA, 168 LRA (7 1/2 HP)-208V AC., (10 HP)-240V AC. 3 PHASE
CLOCK MOTOR: 208-277 VOLTS - 60 HZ.
FOR REPLACEMENT MOTOR, ORDER 131T69GA
WIRING INSTRUCTIONS
This Time Switch can be wired to control one to four circuits simultaneously on a seven
day schedule. Clock motor voltage may be other than load voltage, but  must be as 
specified. For terminal markings, internal wiring and contact arrangements refer to wiring 
diagram above.  Use solid or stranded COPPER wire with insulation to suit installation. See
table for gauge selection.
To make power connections remove 1/2 inch of insulation from wire ends. Insert bare ends
of wire under the pressure plate of terminals. Use 3/16 or larger screw driver to tighten
terminal screws firmly.
REPLACE FRONT INSULATOR BEFORE TURNING
ON ELECTRICITY.
PROGRAMMING INSTRUCTIONS
1.
TO  SET “ON” TIMES, place bright ON trippers against edge of CLOCK-DIAL at
day-of-week and time-of-day when 
“ON” operations are desired. Tighten tripper
screws securely.
2.
TO SET “OFF” TIMES, place dark OFF trippers against edge of CLOCK-DIAL at
times when 
“OFF” operations are desired. Tighten tripper screws securely.
3.
TO SKIP DAYS, omit trippers for the day(s)  automatic operations is/are not required.
4.
TO SET DIAL TO TIME-OF-DAY, turn dial CLOCKWISE and align the exact day-of-
week and time-of-day (AM or PM) on dial with the 
TIME POINTER. Some allowance
may be required to compensate for gear backlash.
CAUTION: DO NOT MOVE POINTER OR FORCE DIAL COUNTERCLOCKWISE.
OPERATING INSTRUCTIONS
• TO OPERATE SWITCH MANUALLY
: Move MANUAL LEVER below CLOCK-DIAL
left or right as indicated by arrows. This will not affect next automatic operation.
• IN CASE OF POWER FAILURE OR TO ADVANCE/RETARD TIME: Reset time-of-
day, see step 4 of programming instructions.
DISCONNECT ELECTRICITY BEFORE ANY BEHIND-THE-INSULATOR WORK.
INTERMATIC INCORPORATED
SPRING GROVE, ILLINOIS 60081-9698
158TS10990
PRESSURE PLATE
TERMINAL SCREW
MAKE SURE WIRE
INSULATION CLEARS
PRESSURE PLATE
MINIMUM
COPPER
WIRE SIZE
(AWG)
MAX.
LOAD
(AMP)
MIN.
INSUL-
ATION
TEMP(°C
75°C INSULATION MAX. MOTOR
LOAD (HP)
SINGLE PHASE
3 PHASE
120 V.
240 V.
208 V.
240 V.
14
12
10
8
15
20
30
40
60
60
60
75
1/2
1
2
-
2
2 1/2
3
5
208
277 V
60 HZ
TO
LOADS
SUPPLY
WIRING DIAGRAM
GROUND
SCREW
3
4
5
7 1/2
3
5
7 1/2
10
CLOCK
MOTOR
A
1
2
3
4
5 6
7 8
B
LR3730
158TS10990  8/6/04  10:29 AM  Page 1