This document provides detailed information on how to install and operate the SG Modular
Series 
of Surge Protective Devices (SPD).
Units should be mounted as close as possible to the AC panel to be protected.  It is recom-
mended that conduit, preferably metallic, be utilized to accomplish this connection.
The SG Modular Series Protectors are installed and connected in parallel ("shunt") across the
AC supply to be protected.  Connecting wires do not carry the supply current, only the short
duration currents associated with the suppression of a transient event.
Identified or indicated terminals must be connected exactly with respect to the AC Power
feeding the SPD.  Failure to do so may result in damage to the device or pose a danger to
personnel.
Incorrect installation may significantly impair the performance of the Surge Protective
Device.  It is particularly  important that all installation procedures and guidelines be followed
exactly.
INSTALLATION OF THIS DEVICE SHOULD ONLY BE PERFORMED BY A
QUALIFIED LICENSED ELECTRICIAN.
Before starting any installation procedures, verify service voltages with an AC Voltmeter to
ensure that the correct SPD Model has been selected.
D
O NOT CONNECT WITHOUT SECURING POWER FROM THE DISTRIBUTION PANEL
.
C
HECK TO ENSURE THAT ALL CONNECTIONS ARE CORRECT AND SECURE BEFORE ENERGIZING
.  D
O
NOT ENERGIZE WITH DOOR OPEN
.
K
EEP THIS MANUAL IN A SAFE DRY PLACE FOR FUTURE REFERENCE
.
A.)
B.)
C.)
D.)
E.)
F.)
G.)
H.)
I.)
J.)
After determining a position to mount the device that
will minimize the length of the connecting  wires,
drill a hole in the cabinet for the conduit to run the
wires from the distribution panel to the connecting
lugs inside the SPD.  Installation is simplified if the
wires enter the enclosure at the top (see figure #2) of
the enclosure.  Securely mount the TVSS unit using
1/4-20 bolts in the four (4) mounting holes provided
in the enclosure's mounting flanges.   
CONSTRUCTION
14 Gauge steel with continuous hinge.
UL 50 Type 12 and Type 13.
NEMA/EEMAC Type 12 and Type 13.
JIC standard #GP-1-1967.
CSA Type 12.
IEC 529, IP65.
[Figure #2:  Cabinet Top View]
[Figure #1:  Cabinet Front View]
10.00"
(254mm)
14.75"
(375mm)
15.50"
(394mm)
12.94"
(329mm)
3.00"
(76mm)
6"
(152mm)
MMOOUUNNTTIINNGG IINNFFOORRMMAATTIIOONN
((AALLLL MMOODDUULLAARR SSGG MMOODDEELLSS))
Page:  2
FINISH
ANSI 61 Gray polyester.
Powder coating inside and
out over phosphatized sufaces.
1.030"
(26.162mm) Dia.
APPLICATION or TECHNICAL ASSISTANCE
Contact Intermatic at 1-800-391-4555 or on the web at www.intermatic.com