INSTEON 2476dbr User Manual

Page of 21
                                                                                                                                  Page 7 of 21                                                                                 Rev: 1/21/2014 7:15 AM 
 
•  Notice that the red traveler wires are not used, so they are capped off at both ends with wire nuts 
o
 
The black traveler wire (traveler 2) is converted to a line wire 
o
 
In SwitchLinc Secondary wall box, connect traveler 2 to the existing line wire and to 
SwitchLinc Secondary line wire 
o
 
In the wall box at the other end of the circuit, connect traveler 2 to SwitchLinc Primary line 
wire 
•  The SwitchLinc Primary load wire is connected to the actual lights being controlled 
•  The load wires on all SwitchLinc Secondaries will not be connected to anything, so cap them off 
with wire nuts 
•  All SwitchLinc modules—Primary and Secondaries—must be connected to neutral and ground 
o
 
SwitchLinc will not function without a neutral 
o
 
The switches you are replacing usually will not have a neutral connection 
o
 
If there is no neutral wire in the wall box, consult an electrician or call the INSTEON 
Support line at 1-800-762-7845 
 
Installing Multi-Way SwitchLinc Modules 
When replacing a 3-way mechanical switch, each switch will have three wires connected to it from the 
wall box. Four- or more-way circuits will have four wires connected to the switches in the center of the 
circuit. For this tutorial, we will follow the most commonly used wire colors for North American homes:  
 
Line wire (also called hot) 
Black 
Neutral wire 
White wire bundle 
Ground wire 
Bare copper, green wire or 
green screw 
Load wire 
Red 
Traveler wires 
Black and/or red 
 
1) 
Disable power at the circuit breaker panel 
2) 
Pull all the switches in the multi-way circuit out of their wall boxes. Each switch should have at 
least three wires connected to it, depending on whether it is a 3-way, 4-way or more-way circuit. 
3) 
Unscrew the wires from the old switches. If the wires cannot be 
unscrewed, cut the wires where they enter the switch and strip ½” of bare 
insulation off the ends. 
4) 
Turn the electricity back on 
Make sure the wires are not touching anything. They are not 
grounded and could cause an electrical shock. 
5) 
Using a voltage meter, individually test and identify each wire (see Fig. 1) 
The wire measuring 120VAC is the line wire (usually black) 
6) 
Turn the electricity back off 
7) 
Connect the wall box line wire and black traveler wire to SwitchLinc 
Secondary line wire. Cap all three wires together with a 
wire nut (see Fig. 2). 
8) 
Cap wall box red traveler wire with a wire nut 
9) 
Cap SwitchLinc Secondary red load wire with a wire nut 
10) 
Locate the neutral wires (usually a white wire bundle) in the rear of the wall 
box. Connect SwitchLinc Secondary white neutral wire to the box neutral 
wires with a wire nut (see Fig. 3) 
11) 
Connect SwitchLinc Secondary bare copper ground wire to the wall box 
ground wires with a wire nut (see Fig. 4) 
12) 
If necessary, install additional SwitchLinc Secondaries by repeating steps 
7-11. See Special Treatment for 4- or More-Way Circuits at the end of this 
section for more information. 
Fig. 1 
Fig. 2 
Fig. 3 
Fig. 4