INSTALLATION INSTRUCTIONS
95-6571-11
L8124A,C,E,L and M
Aquastat® Relays
APPLICATION
These immersion type controllers are used with forced 
hydronic heating systems that include domestic hot water 
service. All models provide high limit, low limit and 
circulator control. Table 1 lists the various models and 
their applications.
These Aquastat® relays have a diaphragm powerhead 
and MicroSwitch™ assembly that respond to 
temperature changes in the boiler water. L8124 can 
provide multizone control by using a separate circulator 
and R845 Relay for each zone. L8124E and L have large 
transformers and extra terminals for supplying power to 
low voltage valves. L8124L  includes a large transformer 
and extra terminals for low voltage zone valves. L8124M 
is for use in a wood-coal/gas-oil multifuel heating system. 
Circulator is independently controlled by the thermostat. 
Do not use these Aquastat® Relays where the pressure 
can exceed 100 psi (690 kPa) on the bulb if inserted 
directly or 200 psi (1380 kPa) when using an immersion 
well, or where the ambient temperature can exceed 
150°F (66°C) at the case or 265°F (129°C) at the sensing 
element.
SPECIFICATIONS
Low Limit:
Setting: 110°F to 220°F (43°C to 104°C), adjustable.
Differential: 10°F to 25°F (6°C to 14°C), adjustable.
High Limit:
Setting: 130°F to 240°F (54°C to 116°C), adjustable.
Differential: 10°F (6°C), fixed.
WARNING
Explosion Hazard.
Can cause serious injury, death or property 
damage.
Use this product only in systems with a pressure 
relief valve.
Table 1. Model Descriptions.
a
 Multizone control can be provided by using a separate circulator and R845 Relay for each zone.
Model 
Number
Burner 
Control 
Circuit
Can Be Used For 
Multizone With 
Circulators
a
No. of V8043 Zone 
Valves Powered 
Without Additional 
Transformer
Electrical Ratings
Burner Circuit
Circulator Circuit
L8124A
120V
Yes
Same as L8124A,C,L 
circulator rating.
120 Vac: 7.4A (full load), 
44.4A (locked rotor).
240 Vac: 3.7A (full load), 
22.2A (locked rotor).
L8124C
L8124L
3
L8124E
24V
2
1.25A at 24 Vac; 30 VA 
(total load) B
1
-B
2
, T
v
-Z.
L8124M 120V
Same as L8124A.
None.