Honeywell m7410f User Manual

Page of 4
M6410A, M7410F ACTUATORS V5862A,V5863A VALVES
63-1293—2
2
Stroke:
1/4 in. (6.5 mm).
Running Time:
At 50 Hz: 150 seconds.
At 60 Hz: 125 seconds.
Stem Force:
67.5 lb (300 N).
Suitable Medium:
Water with maximum 50% glycol.
Controlled Water Temperature:
36° to 230°F (2° to 110°C).
Rangeability:
Two-way Valve: 50:1.
Three-way Valve: 50:1 for controlled port (A to AB).
Flow Characteristic:
Linear.
Valve Cv Rating:
See Table 1.
NOTE: To determine the capacity index (Cv) needed for your 
application, use the following formula: Cv = gallons 
per minute divided by the square root of the pressure 
drop across the valve when the valve is fully open.
Body Material:
Brass.
Stem and Plug Assembly:
Stem: Stainless steel.
Plug: Brass.
Actuator Required:
M6410A: Non-Spring Return Valve Actuator (3-position 
floating).
M7410F: 0 to 10 Vdc or 2 to 10 Vdc Electronic Actuator.
Valve inserts are provided as spare parts. See Table 2.
Leakage Rate:
0.05% of Cv.
Valve Close-off Ratings:
See Table 1.
Approvals (Actuators):
Underwriters Laboratories Inc. listed for plenum use 
(UL94-5V).
Table 1. Valve Close-off Ratings.
a
The Cv for the bypass port (B) on all three-way valves is 
reduced by one Cv level. Example: A Port Cv = 11; 
B Port Cv = 7.8. This feature eliminates the need for a 
balancing valve with the load matched to the proper Cv.
Accessories and Replacement Parts:
WV3000R Insert Replacement Tool, for replacing cartridge 
insert.
Table 2. Valve Insert Replacement Parts.
Pipe Size in 
in. (mm)
C
v
a
Close-off Rating (psi)
Two-way
Three-way
1 (25)
5.5
232
232
7.8
11
1-1/4 (32)
18
174
174
1-1/2 (38)
25
145
145
Diameter (in.)
For Valve
Cv
Part Number
Two-Way
 1
V5862A3003
5.5
0903827
V5862A3011
7.8
V5862A3029
11
1-1/4
V5862A3037
18
0903828
1-1/2
V5862A3045
25
0903829
Three-Way
 1
V5863A3002
5.5
0903827
V5863A3010
7.8
V5863A3028
11
1-1/4
V5863A3036
18
0903828
1-1/2
V5863A3044
25
0903829
M19693