Table 1. Close-off ratings for ML6420, ML7420 Electric Linear Valve Actuators and Honeywell Valves (psi).
a
Represents maximum pressure difference between the outlet and either of the two inlets.
b
Do not exceed 100 psi with V5011G valves used in steam applications.
Fig. 1. Approximate dimensions of ML6420, ML7420 
Electric Linear Valve Actuator in in. (mm).
INSTALLATION
When Installing this Product...
1. Read instructions carefully. Failure to follow them could 
damage the product or cause a hazardous condition.
2. Check ratings and description given in the specifications 
to make sure the product is suitable for your application.
3. Installer must be a trained, experienced service 
technician.
4. After installation is complete, check out product 
operation as provided in these instructions.
CAUTION
Electrical Shock or Equipment Damage Hazard.
Can shock individuals or short equipment circuitry.
Disconnect power supply before installation.
Location
Install the actuator in a location that allows enough clearance 
for mounting accessories and for servicing.
CAUTION
Equipment Damage Hazard.
Can damage actuator due to condensation or a 
valve gland leak.
Install the actuator in a position above horizontal.
Mounting
1. Place the actuator on the valve with the U-bolt around 
the valve collar. See Fig. 2.
2. Place the U-bolt against the valve collar and secure the 
actuator to the valve by turning each U-bolt nut clock-
wise.
NOTE: To assure even pressure on the collar, first 
tighten the nuts finger-tight and then alternate 
turning each U-bolt nut until both are snug.
3. Push aside the stem button retaining clip and hold. See 
Fig. 3.
4. Lift valve stem until the head of the valve stem button is 
inside the large slot of the stem button retaining clip on 
the actuator.
5. Release the stem button retaining clip to secure the stem 
button. Check to make certain the stem button is secured 
by the retaining clip.
6. Remove the cover from the actuator using a Phillips or 
crosspoint screwdriver. See Fig. 4.
Type
Valve
1/2 in.
3/4 in.
1 in.
1-1/4 in. 1-1/2 in.
2 in.
2-1/2 in.
3 in.
Flange
V5011A
28
16
V3350/3351/3450/3451
21
14
V5013B,C; V3360/3361/3460/3461
21
a
14
a
NPT
V5011F,G
150
b
150
b
150
b
134
b
77
49
28
16
V5011H,J
150
150
150
145
V5011N1xxx, V5011N3xxx, V5013N
230
230
163
104
67
37
V5011N2xxx
100
100
100
100
V5013F
150
150
150
126
77
49
5-5/15 
(135)
6-5/16 
(161)
x
2-11/16 (67)
12-11/16 (322)
MINIMUM
CLEARANCE
9-3/16
(233)
9-9/16
(242)
5-9/16
(141)
M17419
1/2 (13) FPT
YOKE 
DIAMETER
1-3/8 (35)