Crestron CLT- & CLX-1DELV4  
Terminal Block & Module 
Module Installation 
NOTE:  Before the five-position bypass jumper, 
shown in the illustration, is removed, the Crestron 
Professional Automation Computer (PAC2), which 
provides control to the system, should be properly 
connected and contain a valid program to provide 
control of the module.  
CAUTION:  Module contains electrostatic sensitive 
devices (ESDs); unit must be handled from metal 
chassis – do not touch PC board or components. 
NOTE:  Modules are to be installed after enclosure 
has been completely wired. Refer to the terminal 
block installation procedure on page 2 for details.  
Wiring Diagram of the Terminal Block to the Module 
(Single-wide and Left Side Double-wide Enclosures) 
       
JUMPER
ENLARGEMENT DETAIL:
LOCATION OF FIVE-POSITION
BYPASS JUMPER ON
TERMINAL BLOCK AS
DESCRIBED IN STEP 5.
JUMPER ON BLACK AND
RED SECTION OF TERMINAL
BLOCK HAS BEEN REMOVED
AFTER LOOSENING ALL SCREWS.
JUMPER ON WHITE SECTION
REMAINS INSTALLED.
ATTACH MODULE
INTERCONNECT CABLE
(DESCRIBED IN STEP 3)
WHITE
BLACK
RED
 
1.  Use the four supplied self-tapping pan Phillips 
screws (8B x ¼ length) to secure the module to 
the enclosure.  
2.  As shown in the wiring diagrams (next column), 
connect the wires from the module to the 
terminal block. Each wire exits the module 
directly in line with, and is the same color as, the 
terminal to which it should be connected. Wires 
are pre-stripped to ½ inch. Tighten to 9 in-lbs. 
Do not over tighten.  
3.  If the module is being installed above another 
module within the enclosure, attach the supplied 
module interconnect cable between the two 
modules. The illustration below depicts the area 
within a double-wide enclosure where the 
corners of four modules meet.  
NOTE:  One wire on the module interconnect cable 
may be a different color from the rest. The color has 
no bearing on its orientation during installation.  
Wiring Diagram of the Terminal Block to the Module 
(Right Side Double-wide Enclosures) 
Use Module Interconnect Cable to Wire Module to Module  
              
MODULE
INTERCONNECT
CABLE ATTACHED
CONNECTION
NOT
MADE
 
       
ATTACH MODULE
INTERCONNECT CABLE
(DESCRIBED IN STEP 3)
ENLARGEMENT DETAIL:
LOCATION OF FIVE-POSITION
BYPASS JUMPER ON
TERMINAL BLOCK AS
DESCRIBED IN STEP 5.
JUMPER ON WHITE SECTION
REMAINS INSTALLED.
JUMPER ON BLACK AND
RED SECTION OF TERMINAL
BLOCK HAS BEEN REMOVED
AFTER LOOSENING ALL SCREWS.
JUMPER
WHITE
BLACK
RED
 
4.  Turn on the circuit breaker and verify that the 
green PWR LED on the module lights, the 
breaker does not trip, and proper loads are 
energized.  
5.  Turn off the circuit breaker and remove the five-
position bypass jumper on the black and red 
section of the terminal block. The bypass jumper 
on the white section of the terminal block 
remains installed. Refer to the figures in the next 
column for a close-up of the jumpers.  
Installation Guide – DOC. 5989A 
Terminal Block & Module:  CLT- & CLX-1DELV4  
  3