Crestron wd cresnet User Manual

Page of 1
        
        
DATA SHEET
CRESNET NETWORK  INTERCONNECT DRAWING
TO
CONTROL SYSTEM
TO
NETWORK DEVICE
SHIELD (SEE NOTE BELOW)
NETWORK DEVICE
TO
TWISTED
PAIR A
PARALLEL
PAIR B
GROUND SHIELD AT CONTROL
SYSTEM END ONLY.
UNTIL ALL WIRING IS VERIFIED.
CARE SHOULD BE TAKEN
TO ENSURE DATA (Y,Z) AND
POWER (24,G) CONNECTIONS
ARE NOT CROSSED.
DO NOT POWER UP SYSTEM
BLACK 18 AWG
RED
WHITE
BLUE
BLACK
WHITE 22 AWG
BLUE 22 AWG
RED 18 AWG
FRONT VIEW
FRONT VIEW
RECOMMENDED COLOR CODE
=
=
=
=
BLUE
WHITE
RED
PAIR A (22 AWG TWISTED)
PAIR B (18 AWG PARALLEL)
        
CAUTION: POSSIBLE EQUIPMENT DAMAGE IF MISWIRED.
RECOMMENDED FOR TESTING PURPOSES AND
DISTRIBUTION/TERMINAL BLOCKS ARE
MODEL CNHBLOCK &/OR CNTBLOCK NETWORK
CONVENIENCE OF WIRING.
FRONT VIEW
1 TO 1 PINOUT REFERENCE
G
24
Y
Z
GND
Z
Y
24
BLACK
CRESTRON ELECTRONICS, INC. ROCKLEIGH, N.J. 1-888-CRESTRON
Specifications subject to change without notice       04.02                 Doc. 5411I
G
24
Y
Z
G
24
Y
Z
G
24
Y
Z
G
24
Y
Z