silent-knight sk-5204 User Manual

Page of 1
Model 5204 Fire Control/Communicator Panel
Built-in Touchpad Operating Instructions
These instructions must be framed and displayed next to the Model 5204 panel
in accordance with NFPA 72 fire code for Local Protected Fire Alarm Systems.
Function
Enter (On Built-in Touchpad):
On 5230, also enter:
System test
0 ENTER
+ Code 0 or 1
Reset alarms (or smoke det.)
1 ENTER  + Code 0 or 1
Same
Clear alarm memory
2 ENTER
+ Code 0 or 1
Reset dialer
3 ENTER  + Code 0
Same
Start download
4 ENTER  + Code 0
Same
Alarm memory display
5 ENTER
+ Code 0 or 1
Display troubles
6 ENTER
+ Code 0 or 1
Silence troubles or alarms
SILENCE
+ Code 0 or 1
Disable/Enable
Zone #1-4 +  DISABLE
+ Code 0 or 1
Same
Begin fire drill
2 0 ENTER  + Code 0
+ Code 0 or 1
End fire drill
SILENCE
+ Code 0 or 1
The system sounds an alarm and reports a fire test when you exit fire drill mode.
Function
Enter (On 
Built-in Touchpad or 5230):
Walk test
2 2 ENTER  + Code 0 *
Zone Troubleshooting mode
2 5 ENTER  + Code 0 *
Step Programming mode
2 7 ENTER  + Code 0 *
Clear (start over if you make a
mistake)
CLEAR
Set time
For example, to set the time of
Wed., 4:30 p.m., enter:
3 1 0 4 3 0
9 ENTER
 
+ 6-digit date
Use 
wdhhmm
 format for time, where:
w   = Day of week (0=Sun., 1=Mon., 2=Tue.,
 3=Wed., 4=Thu., 5=Fri., 6=Sat.)
d    = Time of day (0=AM, 1=PM)
hh  = Hour (enter leading 0 for 1-digit hrs.)
mm = Minutes (enter leading 0 for 1-digit min.)
To exit these modes with the 5230, press  
STEP STEP CLEAR CLEAR
.
   With the built-in touchpad, press  
SILENCE SILENCE CLEAR CLEAR
.
For service call:
Form # 150643  6/95