Puls UBC10.241 DIN-Rail UPS Specification Guide

Page of 23
 
 
 
UBC10.241, UBC10.241-N1 
 
  USeries 
24V, 10A, DC-UPS 
 
 
May. 2008 / Rev. 1.1  DS-UBC10.241-EN 
All parameters are specified at an input voltage of 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time  
unless otherwise noted. It is assumed that the input power source can deliver a sufficient output current. 
www.pulspower.com   Phone +49 89 9278 0    Germany 
1/23 
 
 
DC-UPS
 WITH INTEGRATED BATTERY
 
■ 
Compact and Easy to Install 
■ 
Longest Buffer Time in Class 
■ 
Easy Battery Access 
■ 
Stable Output Voltage in Buffer Mode 
■ 
Superior Battery Management for Longest Battery Life 
■ 
Temperature Compensated Battery Charging 
■ 
Comprehensive Diagnostics and Monitoring Functions 
■ 
Replace Battery Signal Included 
■ 
Electronically Overload and Short Circuit Protected  
■ 
50% Power Reserves 
■ 
Selectable Buffer Time Limiter 
 
 
1.  G
ENERAL 
D
ESCRIPTION
 
 
2.  S
HORT
-
FORM 
D
ATA
 
Input voltage 
nom. 24Vdc 
 
 range 
22.5-30Vdc   
Output current  
min. 15A 
Normal mode 
 
min. 10A  
Buffer mode 
Output voltage 
typ. 0.23V lower 
as input voltage 
Normal mode 
 
22.25V 
Buffer mode, 10A 
Integrated battery  12V 5Ah 
VRLA lead acid 
Temperature range  0 to 40°C 
Operational 
Dimensions 123x124x119mm 
WxHxD 
Buffer time 
typ. 16’15” 
At 5A load 
 
typ. 6’15” 
At 10A load 
This uninterruptible power supply (UPS) controller 
UBC10.241 with integrated battery is a compact 
addition to standard 24V power supplies to bridge 
power failures or voltage fluctuations. Expensive 
downtimes, long restart cycles and loss of data can 
be avoided. 
The DC-UPS includes a professional battery 
management system which charges and monitors 
the battery to achieve the longest battery service life 
as well as many diagnostic functions that ensure a 
reliable operation of the entire system. 
A unique feature of the UBC10.241 is that only one 
12V battery is required to buffer the 24V output. 
This makes matching batteries unnecessary and 
allows a precise battery charging and testing. 
The UBC10.241 has one integrated 12V 5Ah high 
current VRLA battery, which is easy to change. 
In addition to the UBC10.241, a separate UPS 
controller (UB10.241) which requires an external 12V 
battery is available when a longer buffer time is 
required. 
 
Typical setup of a DC-UPS system with the UBC10.241: 
24V
Power 
Supply
UBC10.241
24V
DC-UPS
AC
e.g.: 
Dimension
DC
24V
Load
e.g.: PLC
 
 
 
 
3.  O
RDER 
N
UMBERS
 
 
4.  M
ARKINGS
 
  DC-UPS 
UBC10.241 
Standard unit 
  
UBC10.241-N1  Battery not assembled 
 Accessories  UZB12.051 
Battery 12V 5Ah 
  
 
 
IND. CONT. EQ.
 
UL 508 
 
UL 60950-1 
 
Class I Div 2 
  
 
 
  
 
 
 
 
R
182790
C
US
 
GL
 
Marine 
 
EMC, LVD