Puls YR2.DIODE Redundancy Module Specification Guide

Page of 18
 
 
YR2.DIODE
 
 
Y-Series 
DC12-48V,
 
20A,
 
D
UAL 
R
EDUNDANCY 
M
ODULE
 
 
 
5.  R
ELIABILITY
 
 
The redundancy module does not have electrolytic capacitors included. Therefore, the lifetime expectancy and MTBF 
value is extremely high. 
Input / output  
current conditions 
 
Input: 2x10A
Output: 20A 
Input: 2x5A 
Output: 10A 
 
Lifetime expectancy 
*)
 
min. 
25 years 
25 years 
at 24V and 40°C 
 
min. 
25 years 
25 years 
at 24V and 25°C 
MTBF 
**)
  SN 29500, IEC 61709 
 
46 500 000h 
55 700 000h 
at 24V 40°C 
 
 
70 000 000h 
84 000 000h 
at 24V 25°C 
MTBF 
**)
  MIL HDBK 217F 
 
36 200 000h 
43 500 000h 
at 24Vand 40°C (Ground Benign GB40) 
 
 
41 100 000h 
49 300 000h 
at 24Vand 25°C (Ground Benign GB25) 
*)   The Lifetime expectancy shown in the table indicates the minimum operating hours (service life). 
**)  MTBF stands for Mean Time Between Failure, which is calculated according to statistical device failures, and indicates reliability of a 
device. It is the statistical representation of the likelihood of a unit to fail and does not necessarily represent the life of a product. 
 
 
6.  T
ERMINALS AND 
W
IRING
 
 
 
Input and output 
Type 
Bi-stable, quick-connect spring clamp terminals. 
IP20 Finger safe construction. 
Suitable for field- and factory installation. 
Shipped in open position. 
Solid wire 
0.5-6mm
2
 
Stranded wire 
0.5-4mm
2
 
American Wire Gauge 
20-10 AWG 
Wire stripping length 
10mm / 0.4inch 
Pull-out force 
10AWG:80N, 12AWG:60N, 14AWG:50N, 16AWG:40N (according to UL486E) 
 
Fig. 6-1   Connecting a wire 
 
 
 
1. Insert the wire 
2. Snap the lever 
 
Instructions: 
a)  The external circuitry of all terminals must meet the 
safety requirements stipulated by IEC/EN/UL 60950-1: 
SELV. 
b)  Use appropriate copper cables that are designed for 
minimum operating temperatures of:  
60°C for ambient up to 45°C and  
75°C for ambient up to 60°C minimum. 
c)  Follow national installation codes and installation 
regulations! 
d)  Ensure that all strands of a stranded wire enter the 
terminal connection! 
e)  Up to two stranded wires with the same cross section 
are permitted in one connection point. 
f)  Ferrules are allowed, but not required. 
g)  Do not connect or disconnect the wires from the 
terminals below -25°C (-13°F). 
 
To disconnect wire: same procedure vice versa 
 
May 2010 / Rev. 1.2 DS-YR2.DIODE-EN 