Puls YRM2.DIODE Redundancy Module Specification Guide

Page of 18
 
 
YRM2.DIODE
 
 
Y-Series 
DC24-48V,
 
20A,
 
D
UAL 
R
EDUNDANCY 
M
ODULE
 
 
 
12.  P
ROTECTION 
F
EATURES
 
 
Output over-current protection not 
included 
 
Reverse input polarity protection  included 
unit does not start when input voltage is reversed 
Degree of protection 
IP 20 
EN/IEC 60529 
Penetration protection 
> 3.6mm 
e.g. screws, small parts 
Over-temperature protection 
not included 
 
Input transient protection not 
included 
 
Output transient protection 
included 
see EMC section 
Internal input fuse not 
included  
 
 
 
13.  S
AFETY 
F
EATURES
 
 
Input / output separation 
no galvanic separation 
200V epitaxial diode between input and output 
Safety level of output voltage 
The output voltage is regarded to be SELV (EN 60950-1) or PELV (EN 60204-1, EN 
50178, IEC 60364-4-41) if the input voltage and the voltage which is applied to the 
alarm contacts fulfills the requirements for a SELV source or PELV source. 
Class of protection 
III 
PE (Protective Earth) or chassis connection not required 
PE resistance 
< 0.1Ohm 
between housing and chassis-ground terminal 
 
 
 
14.  D
IELECTRIC 
S
TRENGTH
 
The input and output voltages have the same reference, are floating and have no ohmic connection to ground. 
Type and factory tests are conducted by the manufacturer. Field tests may be conducted in the field using the 
appropriate test equipment which applies the voltage with a slow ramp (2s up and 2s down). Connect 
input/output/signal terminals together before conducting the test.  
When testing, set the cut-off current settings to the value in the table below. 
 
 
Fig. 14-1   Dielectric strength 
 
 
 
A B 
Type test 
60s 
500Vac 
500Vac 
Factory test 
5s 
500Vac 
500Vac 
Field test 
5s 
500Vac 
500Vac 
Cut-off current setting 
> 2mA 
 
 
B
A
DC-ok
Chassis
In- / Output
 -
+
B
 
 
 
 
May 2010 / Rev. 1.2 DS-YRM2.DIODE-EN 
All parameters are specified at 24V, 20A output current, 25°C ambient and after a 5 minutes run-in time unless otherwise noted 