Puls ML15.241 Power Supply Specification Guide
ML15.241
MiniLine
24V,
0.63A,
S
INGLE
P
HASE
I
NPUT
11. T
ERMINALS AND
W
IRING
All terminals are easy to access when mounted on the panel. Input and output terminals are separated from each
other (input below, output above) to help in error-free wiring.
other (input below, output above) to help in error-free wiring.
Input Output
Type
screw terminals
screw terminals
Solid wire
0.5-6mm
2
0.5-6mm
2
Stranded wire
0.5-4mm
2
0.5-4mm
2
American Wire Gauge
20-10 AWG
20-10 AWG
Wire stripping length
7mm / 0.275inch
7mm / 0.275inch
Screwdriver
3.5mm slotted or
Pozidrive No 2
Pozidrive No 2
3.5mm slotted or
Pozidrive No 2
Pozidrive No 2
Recommended tightening torque
1Nm, 9lb.in
1Nm, 9lb.in
Instructions:
a) Use appropriate copper cables that are designed for minimum operating temperatures of:
a) Use appropriate copper cables that are designed for minimum operating temperatures of:
60°C for ambient up to 45°C and 75°C for ambient up to 60°C minimum.
b) Follow
national installation codes and installation regulations!
c) Ensure that all strands of a stranded wire enter the terminal connection!
d) Up to two stranded wires with the same cross section are permitted in one connection point (except PE wire).
e) Do not use the unit without PE connection.
f) Screws of unused terminal compartments should be securely tightened.
g) Ferrules are allowed, but not required
d) Up to two stranded wires with the same cross section are permitted in one connection point (except PE wire).
e) Do not use the unit without PE connection.
f) Screws of unused terminal compartments should be securely tightened.
g) Ferrules are allowed, but not required
12. R
ELIABILITY
These units are extremely reliable and use only the highest quality materials. The number of critical components such
as electrolytic capacitors has been reduced.
as electrolytic capacitors has been reduced.
AC 100V
AC 120V
AC 230V
Lifetime expectancy
*)
197 000h
200 000h
196 000h
at 24V, 0.63A and 40°C
> 15 years
> 15 years
> 15 years
at 24V, 0.315A and 40°C
> 15 years
> 15 years
> 15 years
at 24V, 0.63A and 25°C
MTBF
**)
SN 29500, IEC 61709 4 016 000h
4 360 000h
4 369 000h
at 24V, 0.63A and 40°C
6 586 000h
7 150 000h
7 165 000h
at 24V, 0.63A and 25°C
MTBF
**)
MIL HDBK 217F
1 112 000h
1 169 000h
1 095 000h
at 24V, 0.63A and 40°C; Ground Benign GB40
1 490 000h
1 566 000h
1 467 000h
at 24V, 0.63A and 25°C; Ground Benign GB25
*) The Lifetime expectancy shown in the table indicates the minimum operating hours (service life) and is determined by the lifetime
expectancy of the built-in electrolytic capacitors. Lifetime expectancy is specified in operational hours and is calculated according to the
capacitor’s manufacturer specification. The prediction model allows only a calculation of up to 15 years from date of shipment.
capacitor’s manufacturer specification. The prediction model allows only a calculation of up to 15 years from date of shipment.
**) MTBF stands for Mean Time Between Failure, which is calculated according to statistical device failures, and indicates reliability of a
device. It is the statistical representation of the likelihood of a unit to fail and does not necessarily represent the life of a product.
Oct. 2009 / Rev. 1.2 DS-ML15.241-EN