Puls CS10.241 Power Supply Specification Guide

Page of 20
 
 
 
CS10.241, CS10.241-S1 
 
  CSeries 
24V, 10A, S
INGLE 
P
HASE 
I
NPUT
 
 
 
August 2006 / Rev. 1.1  DS-CS10.241-EN / All parameters are specified at 24V, 10A, 230Vac and 25°C ambient unless otherwise noted. 
www.pulspower.com   Phone +49 89 9278 0    Germany 
14/20 
 
22. P
HYSICAL 
D
IMENSIONS AND 
W
EIGHT
 
 
  Weight 
700g / 1.54lb 
 
  DIN-Rail 
Use 35mm DIN-rails according to EN 60715 or EN 50022 with a height of 7.5 or 15mm.  
The DIN-rail height must be added to the depth (117mm) to calculate the total required 
installation depth. 
  Electronic files with mechanical data can be downloaded at www.pulspower.com 
 
 
Fig. 22-1   Front view 
 
Fig. 22-2   Side view 
 
 
 
 
 
 
23. I
NSTALLATION AND 
O
PERATION 
I
NSTRUCTIONS
 
 
Mounting Orientation: 
Output terminal must be located on top and input terminal on the bottom. For other orientations consult factory.  
Cooling: 
Convection cooled, no forced cooling required. Do not cover ventilation grid (e.g. cable conduit) by more than 30%!  
Installation clearances: 
40mm on top, 20mm on the bottom, 5mm on the left and right side are recommended when loaded permanently 
with full power. In case the adjacent device is a heat source, 15mm clearance are recommended. 
Risk of electrical shock, fire, personal injury or death! 
Do not use the unit without proper earth connection (Protective Earth). Use the pin on the terminal block for earth 
connection and not one of the screws on the housing. 
Turn power off before working on the power supply. Protect against inadvertent re-powering. 
Make sure the wiring is correct by following all local and national codes. 
Do not  open, modify or repair the unit. 
Use caution to prevent any foreign objects from entering into the housing. 
Do not use in wet locations or in areas where moisture or condensation can be expected. 
Service parts: 
The unit does not contain any service parts. The tripping of an internal fuse is caused by an internal defect. If damage 
or malfunctioning should occur during operation, immediately turn power off and send unit to factory for 
inspection!