Redundancy functions
MRP (Media Redundancy Protocol IEC62439-2), RSTP 802.1D-2004 (IEC62439-1), Link Aggregation (2 LAG), Link backup; default Standard
Industrial Profiles
IEC61850 protocol (MMS Server, Switch Model)
Filter
QoS (8 classes), CoS queue management, interface trust mode, TOS/DSCP prioritization, port priority (IEEE802.1D/p), VLAN (IEEE802.1Q), Voice VLAN, IGMP
snooping/querier per VLAN (v1/v2/v3), unkown multicast filtering, independent VLAN learning, static unicast/multicast address entries, fast aging, MVRP
(Multiple VLAN Registration Protocol), MMRP (Multiple MAC Registration Protocol), MRP (Multiple Registration Protocol)
Time synchronisation
SNTP server and client, Buffered RTC
Flow control
Flow control (IEEE802.3X), egress interface shaping, ingress storm protection, Queue-Shaping / max. Queue Bandwidth
Miscellaneous
Port power down, cable crossing, dual software image support, VLAN unaware mode, access to management restricted by VLAN
Ambient conditions
Operating temperature
0 ºC ... 60 ºC
Storage/transport temperature
-40 ºC ... 70 ºC
Relative humidity (non-condensing)
5 % ... 95 %
Mechanical stability
IEC 60068-2-27 shock
15 g, 11 ms duration, 18 shocks
IEC 60068-2-6 vibration
1 mm, 2 Hz-13.2 Hz, 90 min.; 0.7 g, 13.2 Hz-100 Hz, 90 min.; 3.5 mm, 3 Hz-9 Hz, 10 cycles, 1 octave/min.; 1 g, 9 Hz-150 Hz, 10 cycles, 1 octave/min
EMC interference immunity
EN 61000-4-2 electrostatic discharge (ESD)
8 kV contact discharge, 15 kV air discharge
EN 61000-4-3 electromagnetic field
35 V/m (80-2700 MHz); 1 kHz, 80% AM
EN 61000-4-4 fast transients (burst)
4 kV power line, 4 kV data line
EN 61000-4-5 surge voltage
power line: 2 kV (line/earth), 1 kV (line/line), 1 kV data line, IEEE1613: power line 5 kV (line/earth)
EN 61000-4-6 conducted immunity
3 V (10 kHz-150 kHz), 10 V (150 kHz-80 MHz)
EN 61000-4-16 mains frequency voltage
30 V, 50 Hz continous; 300 V, 50 Hz 1 s
EMC emitted immunity
FCC CFR47 Part 15
FCC 47 CFR Part 15 Class A
EN 55022
EN 55022 Class A
Approvals
Safety of industrial control equipment
EN61131, EN60950
Substation
IEC61850, IEEE1613
Scope of delivery and accessories
Scope of delivery
Device, terminal block, operating manual
Accessories to order separately
Terminal Cable, Network management Industrial HiVision, ACA22, SFP
For more information please contact:
Hirschmann Automation and Control GmbH
Stuttgarter Strasse 45-51
72654 Neckartenzlingen
Germany
Phone: +49 7127/14-1809
E-Mail: inet-sales@belden.com
 
The information published in the websites has been compiled as carefully as possible. It is subject to alteration without notice in technical as well as in price-related/commercial respect.
The complete information and data were available on user documentation. Mandatory information can only be obtained by a concrete query.