Hirschmann GRM20-TTTTTTTTSV9HHS Module Specification Guide

Page of 2
 
Hirschmann Automation and Control GmbH  
www.beldensolutions.com
 
09-02-2015
Page 1 of 2
 
Product information
Greyhound Module - GRM20-TTTTTTTTSV9HHS
Industrial Ethernet:Ruggedized Switches:GREYHOUND Gigabit Ethernet Switch and Media Modules:Greyhound Module
http://www.e-catalog.beldensolutions.com/link/57078-24455-49846-433327-433609/en/GRM20-TTTTTTTTSV9HHS/uistate
Name
Greyhound Module
 
Fast Ethernet media module
Delivery informations
Availability
available
Product description
Type
GRM20-TTTTTTTTSV9HHS
Order No.
GRM20-TTTTTTTTSV9HHS
Description
Fast Ethernet media module
Port type base unit
8 x ports in total; 8 x FE/RJ45;
Network size - length of cable
Twisted pair (TP)
0 m ... 100 m
Power requirements
Operating voltage
power supply via GREYHOUND switch
Power consumption
10.0
Ambient conditions
Operating temperature
0 ºC ... 60 ºC
Storage/transport temperature
-40 ºC ... 70 ºC
Relative humidity (non-condensing)
5 % ... 95 %
Mechanical construction
Weight
450g - 650g depending on variant
Protection class
IP30
Mechanical stability
IEC 60068-2-27 shock
15 g, 11 ms duration, 18 shocks
IEC 60068-2-6 vibration
1 mm, 2 Hz-13.2 Hz, 90 min.; 0.7 g, 13.2 Hz-100 Hz, 90 min.; 3.5 mm, 3 Hz-9 Hz, 10 cycles, 1 octave/min.; 1 g, 9 Hz-150 Hz, 10 cycles, 1 octave/min
EMC interference immunity
EN 61000-4-2 electrostatic discharge (ESD)
8 kV contact discharge, 15 kV air discharge
EN 61000-4-3 electromagnetic field
35 V/m (80-2700 MHz); 1 kHz, 80% AM
EN 61000-4-4 fast transients (burst)
4 kV power line, 4 kV data line
EN 61000-4-5 surge voltage
power line: 2 kV (line/earth), 1 kV (line/line), 1 kV data line, IEEE1613: power line 5 kV (line/earth)
EN 61000-4-6 conducted immunity
3 V (10 kHz-150 kHz), 10 V (150 kHz-80 MHz)
EN 61000-4-16 mains frequency voltage
30 V, 50 Hz continous; 300 V, 50 Hz 1 s
EMC emitted immunity
FCC CFR47 Part 15
FCC 47 CFR Part 15 Class A
EN 55022
EN 55022 Class A
Approvals
Safety of industrial control equipment
EN61131, EN60950
Substation
IEC61850, IEEE1613
Scope of delivery and accessories
Scope of delivery
Device