Moxa ioLogik E2262 Specification Guide

Page of 2
1
w w w. m o x a . c o m
i n f o @ m o x a . c o m
Industrial I/O
Active Ethernet I/O with 8 thermocouple inputs and 4 digital outputs 
ioLogik E2262
Supports J, K, T, E, R, S, B, and N type thermocouple and  
 
mV modes
Conversion Time: Less than 90 ms
 
Instant event messaging by TCP/UDP/email/SNMP-Trap
 
PC-based configuration utility and web console 
 
Easy-to-use Click&Go™ Logic for local output control
 
Windows/WinCE VB/VC.NET and Linux C APIs
 
I/O control over Modbus/TCP and SNMP protocol
 
NIST traceable calibration
 
Introduction
Extend the Wiring Length
The ioLogik E2262 can extend the wiring length of your sensors up to 
10 fold. For example, whereas the wiring for a J-Type may normally 
extend only 10 m, the ioLogik E2262 can be used to increase the 
J-Type TC wiring length up to 100 m.
Specifications
LAN
Ethernet: 1 x 10/100 Mbps, RJ45
Protection: 1.5 KV magnetic isolation
Protocols: Modbus/TCP, TCP/IP, UDP, DHCP, Bootp, SNMP (MIB for 
I/O and Network), HTTP, CGI, SNTP
Serial Communication
Interface: RS-485-2w: Data+, Data-, GND
Serial Line Protection: 15 KV ESD for all signals
Serial Communication Parameters
Parity: None
Data Bits: 8
Stop Bits: 1
Flow Control: None
Baudrate: 1200 to 115200 bps
Protocol: Modbus/RTU
Thermocouple Input
Channels: 8
Sensor Type: J, K, T, E, R, S, B, N type TC and mV mode
Conversion Time: Less than 90 ms 
Effective Resolution: 16 bits
Accuracy:  
±0.1% FSR @ 25°C 
±0.3% FSR @ -10 and 60°C
Input Impedance: 1 M ohm or better
Digital Output
Channels: 4, sink type, 36 VDC, 200 mA
I/O Mode: DO or Pulse Output (up to 100 Hz) 
Pulse Wave Width/Frequency: 10 ms/100 Hz
Over-voltage Protection: 45 VDC
Over-current Limit: 750 mA
Over-temperature Shutdown: 175°C
Isolation: 3K VDC or 2K Vrms
Power Requirements
Power Input: 24 VDC nominal, 12 to 48 VDC
Power Consumption: 282 mA typical @ 24 VDC
Physical Characteristics 
Wiring: I/O cable max. 14AWG
Dimensions: 115 x 79 x 45.63 mm (4.53 x 3.11 x 1.8 in)
Weight: 210 g
Environmental Limits
Operating Temperature: -10 to 60°C (14 to 140°F)
Storage Temperature: -40 to 85°C (-40 to 185°F)
Ambient Relative Humidity: 5 to 95% (non-condensing)
More Accurate Temperates
The ioLogik E2262 has two cold junction compensation sets and 
supports digital filtering. Calibration, linearization, and calculation 
are based on the devices traced by the NIST (National Institute of 
Standards and Technology), and are stored in memory to eliminate 
this source of error. The ioLogik E2262 can also detect burnout and 
disconnection.