Moxa M-4402 Output Module Specification Guide
1
w w w. m o x a . c o m
i n f o @ m o x a . c o m
Industrial I/O
ioLogik E4200
Introduction
The ioLogik E4200 is suitable for remote monitoring and alarm
systems, such as are used for water treatment systems, water supply
systems, wastewater treatment systems, and power monitoring
systems. These kinds of applications need more I/O points and a
systems, such as are used for water treatment systems, water supply
systems, wastewater treatment systems, and power monitoring
systems. These kinds of applications need more I/O points and a
Supports up to 16 I/O modules
›
Dual Ethernet LANs and one RS-232 port
›
Front-end intelligence that supports 80 Click&Go rules
›
Unicode Active Messaging with real-time stamp, including SMS,
›
SNMP Trap with I/O status, TCP, email
Built-in web console
Built-in web console
›
PC utility: Auto detection of installed modules
›
Windows/WinCE VB/VC.NET and Linux C APIs
›
Specifications
Modular Active Ethernet I/O adaptor
variety of I/O types, including temperature sensors, gas detectors,
and water quality detectors, all of which can benefit from the versatile
mixture of I/O features supported by the ioLogik E4200.
and water quality detectors, all of which can benefit from the versatile
mixture of I/O features supported by the ioLogik E4200.
LAN
Ethernet: 2 x 10/100 Mbps (2 MACs, 2 IPs, RJ45 connectors)
Protection: 1.5 KV magnetic isolation
Protocols: Modbus/TCP, TCP/IP, UDP, DHCP, Bootp, SNMP, SNMP
Trap, HTTP, SNTP
Protection: 1.5 KV magnetic isolation
Protocols: Modbus/TCP, TCP/IP, UDP, DHCP, Bootp, SNMP, SNMP
Trap, HTTP, SNTP
Serial Communication
Interface: 1 x RS-232/485 (9-pin D-Sub, male)
Parameters: N, 8, 1
Baudrate: 115,200 bps
Parameters: N, 8, 1
Baudrate: 115,200 bps
Power Requirements
Power Input: 24 VDC nominal, 12 to 36 VDC
Power Consumption: 60 mA typical @ 24 VDC
Current for I/O Modules: Max. 1.5A @ 5 VDC
Power Consumption: 60 mA typical @ 24 VDC
Current for I/O Modules: Max. 1.5A @ 5 VDC
Field Power
Rated Voltage: 11 to 28.8 VDC, 24 VDC typical
Current in Field Power Contact: Max. 10 A
Current in Field Power Contact: Max. 10 A
Isolation
System Power to I/O Driver: Optical isolation
Physical Characteristics
Dimensions: 45 x 99 x 70 mm (1.77 x 3.9 x 2.76 in)
Weight: 180 g
Weight: 180 g
Environmental Limits
Operating Temperature: -10 to 60°C (14 to 140°F)
Storage Temperature: -40 to 85°C (-40 to 185°F)
Ambient Relative Humidity: 5 to 95% (non-condensing)
Storage Temperature: -40 to 85°C (-40 to 185°F)
Ambient Relative Humidity: 5 to 95% (non-condensing)
Regulatory Approvals
EMI: FCC part 15, CISPR (EN55022) Class A
EMS:
IEC 61000-4-2 (ESD), level 2/3
IEC 61000-4-3 (RS), level 2
IEC 61000-4-4 (EFT), level 2
IEC 61000-4-5 (Surge), level 3
IEC 61000-4-6 (CS), level 2
IEC 61000-4-8 (PM), level 1
IEC 61000-4-11 (DIP)
IEC 61000-6-2 (ESD), level 2/3
IEC 61000-6-4 (EFT), level 2
Safety: UL 508
Shock: IEC 60068-2-27
Freefall: IEC 60068-2-32
Vibration: IEC 60068-2-6
EMS:
IEC 61000-4-2 (ESD), level 2/3
IEC 61000-4-3 (RS), level 2
IEC 61000-4-4 (EFT), level 2
IEC 61000-4-5 (Surge), level 3
IEC 61000-4-6 (CS), level 2
IEC 61000-4-8 (PM), level 1
IEC 61000-4-11 (DIP)
IEC 61000-6-2 (ESD), level 2/3
IEC 61000-6-4 (EFT), level 2
Safety: UL 508
Shock: IEC 60068-2-27
Freefall: IEC 60068-2-32
Vibration: IEC 60068-2-6
Note: Please check Moxa’s website for the most up-to-date certification status.
Warranty
Warranty Period: 2 years
Details: See www.moxa.com/warranty
Details: See www.moxa.com/warranty