Chapter 4 Removal and Replacement Procedures
Removing and Installing the DC-Input Power Supplies
Step 4
Disconnect the DC-input wires from the terminal block (see
for the 1300 W DC power
supply or
for the 2500 W DC power supply) in this order:
1.
Positive (+)
2.
Negative (–)
3.
Ground
Note
The terminals on the 1300 W DC power supply DC power cable terminal block are labeled (from
top to bottom) +, –, ground. The terminals on the 2500 W DC power supply DC power cable
terminal block are labeled (from top to bottom) –, +, ground.
top to bottom) +, –, ground. The terminals on the 2500 W DC power supply DC power cable
terminal block are labeled (from top to bottom) –, +, ground.
Step 5
Loosen the captive installation screw on the power supply. (See
for the 1300 W DC power
supply or
for the 2500 W DC power supply.)
Caution
Use both hands to install and remove power supplies. Each Catalyst 6500 series DC-input power supply
weighs between 22 pounds (10 kg) and 33 pounds (15 kg).
weighs between 22 pounds (10 kg) and 33 pounds (15 kg).
Step 6
Grasp the power supply handle with one hand, and slide the power supply halfway out of the chassis.
Place your other hand underneath the power supply, as shown in
Place your other hand underneath the power supply, as shown in
, and slide the power supply
completely out of the chassis. Set the power supply aside.
Step 7
If the power supply bay is to remain empty, install a blank faceplate (Cisco part number 700-03104-01)
over the opening, and secure it with the captive installation screw.
over the opening, and secure it with the captive installation screw.
Figure 4-11 DC-Input Power Supply Front Panel (WS-CDC-1300W)
16028
Power
switch
switch
DC power cable
terminal block
Terminal block
cover
cover
INPUT
OK
FAN
OK
OUTPUT
FAIL
I
0
Status LEDs
Captive installation
screw