Tripp Lite SmartOnline 3-Phase In/Out 208/120V 20kVA 16kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 12U Rack/Tower, DB9 Serial, Hardwire SU20K3/3XR5 User Manual

Product codes
SU20K3/3XR5
Page of 6
Built-in UPS output
receptacles
Hardwire
Output AC
waveform (AC
mode)
Sine wave
Output AC
waveform (battery
mode)
Pure Sine wave
INPUT
Rated input current
(at maximum load)
60A (per phase, online)
Nominal Input
Voltage(s)
Supported
120V / 208V 3 phase wye
UPS input
connection type
Hardwire
UPS input
connection
description
120/208V (3-Phase, 4 Wire, wye)
BATTERY
Full load runtime
(minutes)
17 min. (16kw)
Half load runtime
(minutes)
42 min. (8kw)
Expandable battery
runtime
Supports extended runtime with optional external battery packs
External battery
pack compatibility
)
Expandable
runtime description
 batteries - see runtime chart for
specific recommendations
DC system voltage
(VDC)
240
Battery recharge
rate (included
batteries)
2 - 4 hours from 10% to 90%
Replacement
battery cartridge
(internal UPS
battery
replacement)
Battery Access
Front panel internal battery access door
Battery
replacement
description
Hot-swappable, replaceable batteries
VOLTAGE REGULATION
Voltage regulation
description
Online, double-conversion power conditioning
Overvoltage
correction
Maintains continuous operation without using battery power during overvoltages to 144 / 250 (3-Phase, 4-Wire, wye),
reducing output within 2% of nominal