3)  SIGNAL SENSOR (WS200):  Save time and possible lost data by using 
the Signal Sensor before installing Loggers and Repeaters. 
a)  Once the Receiver has been installed, go to each designated Logger 
location, with the Signal Sensor, to determine if the Receiver signal 
strength will be strong enough to reach the Logger location. (See Signal 
Sensor Operating Instructions below.) 
b)  The display will indicate if the Receiver can be found and how strong the 
signal is. 
c)  If two bars or less show or if the signal strength changes frequently a 
Repeater will be required to ensure consistent communication of the 
Logger to the Receiver. 
d)  Repeat for all Logger placement locations. 
e)  If it has been determined that a Repeater(s) is required, install the 
Repeater(s) first and link each Logger to its designated Repeater when 
installing. 
f)  The Signal Sensor is ideal for determining if the target Logger location is 
within range of the Receiver or Repeater. 
g)  Signal Sensor Operation: 
i)  Press the On/Off button once on your signal sensor to turn on.   
ii)  Move to the location where you wish to place a Logger or Repeater.  
iii)  Stand at the target Logger/Repeater location for a couple of minutes.  
The Signal Sensor will indicate if it can see the Receiver or other 
Repeaters and display signal strength.  (The signal sensor does not 
look for Loggers.) 
iv)  If a Repeater or Receiver is found and more than two bars are 
displayed, the target location is good.  
v)  If a Repeater or Receiver can not be located or displays two bars or 
less, move closer to known Repeater or Receiver locations until a 
stronger signal is found. 
Signal Sensor (WS200)
 
Did you purchase a Repeater(s)? 
Yes: See Repeater Installation below 
No: Skip to the Installing Loggers section