CM xx WR OPERATIONAL SETTINGS
  
 
Heartbeat Settings
Frequency that the sensor will transmit status 
information.
Step 1. Press and release button 3 times
Step 2. LED will flash back current setting
Step 3. To change setting, press button the number 
of increments of  the new setting from below list:
  1 - 30 sec           2 - 2.5 min         3 - 5.0 min*
Step 4. LED will flash back new setting (repeats 3 
times, then exits)
Test Mode
Temporarily sets heartbeat time to 5 sec and              
     
flashes LED whenever occupancy is detected. 
To Enter test mode:
Step 1. Press and release button 6 times
Step 2. Wait until LED begins to flash back 
Step 3. Press and release button twice
To Exit test mode:
Step 1. Press and release button 6 times
Step 2. Wait until LED begins to flash back 
Step 3. Press and release button once
Notes: 
1. Test mode expires automatically after 10 min
2. Paired SPODMR WR units will also enter and                  
              
exit Test Mode simultaneously with sensor
3. Dual Technology disabled while in Test Mode
Microphone On Time**
Duration that the microphone will stay on after the last 
occupancy transmission.
Step 1. Press and release button 4 times
Step 2. LED will flash current setting
Step 3. To change setting, press button the number of 
increments of  the new setting from below list:
  1 - 45 sec  
4 - 7.75 min  
- 15.25 min
  2 - 2.75 min  5 
- 10.25 min*
  3 - 5.25 min   
- 12.75 min
Step 4. LED will flash back new setting (repeats 3 times, 
then exits)
Microphone Setback Time**
Duration the microphone stays on without sensor ever 
detecting motion via PIR.
Step 1. Press and release button 5 times
Step 2. LED will flash current setting
Step 3. To change setting, press button the number of 
increments of  the new setting from below list:
  1 - 15 min   
3 - 45 min 
5 - Infinite
  2 - 30 min  4 - 1 hr*
 
Step 4. LED will flash back new setting (repeats 3 times, 
then exits)
Teach
Transmits sensor ID to facilitate pairing with other 
devices. 
Step 1. Press and release button 2 times
Step 2. LED will rapid flash when transmitting
Note: Sensor resumes normal operation after one 
transmission is sent
Reset
Returns unit to orignal factory settings.
 
Step 1. Press and release button 9 times
Step 2. LED will flash once
Step 3. Press and release button 2 times 
Step 4. LED will flash back twice (repeats 3 times, 
then exits and resets)
Use push-button on side of sensor to 
change settings.
       *  Denotes factory setting
       **Applies to Dual Technology (-PDT)
            sensors only
 
 
1. Screw battery extension ring to ceiling 
using included pointed tip screws (qty 2)
INSTALLATION INSTRUCTIONS
2. Plug battery connector into 
back of sensor
3. Screw sensor to battery extension ring 
using included flat tipped screws (qty 2) 
AA Lithium
AA Lithium