Tyco Safety Products / Software House PI26 User Manual
Connecting to a Host Computer
4-2
apC/8X Technical Manual
Connecting to a Host Computer
The host port P32 connects the apC/8X to a host computer (see Figure 4.1).
A single apC/8X can connect to the host via an RS-232 serial
connection.
Multiple apC/8Xs communicate via an RS-485 chain, but the apC/8X
chain must communicate with the host through an RS-232 to RS-485
converter.
connection.
Multiple apC/8Xs communicate via an RS-485 chain, but the apC/8X
chain must communicate with the host through an RS-232 to RS-485
converter.
Figure 4.1: RS-232 Three-wire Connection between apC/8X and Host
You can use modems, line drivers, or other communications devices to
increase the distance between the host and the apC/8X.
increase the distance between the host and the apC/8X.
The following sections describe these connections:
RS-232
RS-485
Modems for dialup apC/8Xs
Modems for directly connected apC/8Xs
RS-485
Modems for dialup apC/8Xs
Modems for directly connected apC/8Xs
TX
RX
GND
TX
RX
GND
apC/8X
Host
Host PC
RS-232
Twisted, shielded 22 AWG (.325 mm)
Belden 9855 or equivalent
Maximum 50 feet (15 meters) without modems or line drivers
Maximum 50 feet (15 meters) without modems or line drivers
1
2
3
4
5
P32
port