Eaton PC975-LT User Manual

Page of 5
© 2008 Eaton Corporation. All Rights Reserved. All specifications are subject to change without notice.
www.pulizzi.com • pulizzisales@eaton.com • 800-870-2248 • Fax: 605-334-4999 
2
SPECIFICATIONS
PC975, PC975-LT
PC975-1969, PC975-1969/LT
PC975-2109, PC975-2109-LT
Approvals
UL/cUL
UL/cUL
UL/cUL
Voltage Input Three Phase (50/60Hz)
120/208V
120/208V
120/208V
Voltage Output (50/60Hz)
120V~ and 208V~
120V~ and 120/208V~
120V~
Current Input Per Phase
30A Per Phase
30A Per Phase
30A Per Phase
Current Output Per Phase
24A Per Phase
24A Per Phase
24A Per Phase
Full Load VA Per Phase
2880VA Per Phase
2880VA Per Phase
2880VA Per Phase
Main Circuit Breaker (on/off switch)
4 Pole 30/30/30/30
4 Pole 30/30/30/30
4 Pole 30/30/30/30
Secondary Circuit Breakers Per Phase
(3) 2 Pole 20/20
N/A
(3) 1 Pole 20
Unswitched Duplex Circuit Breaker
20A thermal reset
20A thermal reset
15A thermal reset
EMI/RFI Filter
30A
30A
30A
Surge Suppression
270V
270V
270V
NEMA Outlets
(8) 5-20R and (3) L6-20R
(8) 5-20R and (3) L21-30R
(8) 5-15R and (3) L5-30R
Power Cord/Length/Plug
10/5, 15’, L21-30P
10/5, 15’, L21-30P
10/5, 15’, L21-30P
RACK MOUNTED
19” x 3.4” (2U) x 14.5” 
(Including 2.5” recess)
Approximate shipping weight: 29 lbs.
EMI/RFI FILTERING
Common Mode - Line to Ground
Differential Mode - Line to Line
SPIKE/SURGE SUPPRESSION
270V MOV L-N
(11) NEMA OUTLETS
(2) Unswitched outlets
(1) Duplex and (1) twist lock per Phase
(4) INDICATOR LIGHTS
Main breaker power “on” 
Power “on” to PH-X, Y and Z
OVERLOAD CIRCUIT PROTECTION
Electromagnetic breakers, with  
 
a long time delay curve, provide both  
 
manual on/off switching and trips  
 
automatically in an overload condition
LOCAL/OFF/REMOTE SWITCHING
Local: Power “on or off” to the switched  
 
outlets
Off: When breaker is “on” but this switch  
 
is in the “off” mode, you will have power  
 
to the unswitched outlets only
Remote: Power “on or off” to the  
 
switched outlets via a remote device
When using the Latching remote option,  
 
the selection switch is wired for  
 
Remote/Off/Remote - There is no local  
 
control
MULTIPLE TIME DELAY™ (MTD™)
Activated “Locally” or “Remotely”, PH-X  
 
powers up, followed 4-seconds later by  
 
PH-Y, which is followed 4-seconds later  
 
PH-Z, then 4-seconds later the  
 
sequenced remote activates the next 
system in line
(4 N/O) REMOTE I/O PORTS
Remote on/off and EPO control, EPO  
 
overrides remote and local control
Sequence Power Up additional 
equipment down line (standard on all units)
Latching remote - (N/C) EPO, 
momentary start.  “LT” systems
POWER INPUT
Power cable with plug is attached to unit    
through the front panel cable grip
Call the factory for other outlet configurations: 1-800-870-2248
PC975-LT Rear
PC975-LT Front