RadioFrame Networks Inc DH2 User Manual

Page of 164
Method of Procedure 
Pre-Installation 
56 
RFN_3.1 Beta
 
Cables shall be separated by at least 5.1 cm (2 in.) from AC power conductors. 
Refer to NFPA 70, Article 800-52 for more information. 
CAT 5 cables installed in ducts, plenums, and other air-handling spaces shall be 
installed in accordance with other sections of this document and NFPA 70, Article 
300-22. Also refer to NFPA 70, Article 645. 
 
CAT 5 cables installed in hazardous areas as defined in NFPA 70, Article 500 
shall be installed in accordance with NFPA 70, Article 500 and any other 
applicable electrical and building codes. 
CAT 5 cable shall not be attached by any means to the exterior of a conduit or 
other raceway as a means of support. Refer to NFPA 70, Article 725-54 and 
NFPA 70, Article 800-52 for more information.  
Suspended ceiling support rods and wires may be used as a means of support 
for computer network cabling if used in conjunction with appropriate cable 
fasteners. Refer to ANSI/TIA/EIA-569-A and CSA-T530 for more information.  
CAT 5 cables shall not be laid directly on the tiles of a false ceiling. Refer to 
ANSI/TIA/EIA-569-A and CSA-T530 for more information.  
CAT 5 cables shall not be run from one building to another building. If the 
computer network needs to 
be 
extended to another building, a specific cabling 
system shall be engineered. Options for extending from one building to another 
may include the 
use 
of fiber optic cable or a T1. Computer network cabling 
entering and/or leaving a building shall be properly grounded and protected from 
surges as required elsewhere in this document. 
3.9.4.4 Testing 
Every effort should be made to ensure a quality installation of the computer 
network cabling system. Even the best installation effort cannot guarantee a 
properly working system. It is therefore required that a computer network cabling 
system be tested for proper performance. 
The procedures and specifications in the TIA/EIA Telecommunications System 
Bulletin (TSB) 67 shall be used for this testing. TSB 67 has four primary 
parameters to test. Below is an overview of the four test parameters needed to 
assure a properly working system. 
Wire map 
The wire map test is used to verify wire pair to pin termination at each end of the 
cable and to check for installation connectivity errors. It is recommended that 
100% of cables be tested using a testing tool such as Microtest® Microscanner™ 
Pro. (Be sure the tester can check for a “split pair” configuration).  
Each of the 8 conductors in the cable are tested for: 
• 
Conductor continuity to the remote end of the cable