Riello Sentinel Dual 10000VA CSDLK10TA5 User Manual

Product codes
CSDLK10TA5
Page of 5
52
MODELS
SDL 6500 TM
SDL 8000 TM
SDL 10000 TM
PoWeR
6500va/5200W
8000va/6400W
10000va/8000W
inPuT
nominal voltage
400 Vac Three-phase + N
minimum voltage (f + n)
164 Vac @ load 100% / 84 Vac @ load 50%
nominal frequency
50 or 60 Hz ±5Hz
Power factor
> 0.95
By Pass
voltage tolerance
180 - 264 Vac (selectable in Economy Mode or Smart Active Mode)
frequency tolerance
Selected frequency ±5% (selectable by user)
ouTPuT
nominal voltage
220-230-240 Vac selectable
voltage distortion
< 3% with linear load / < 6% with non-linear load
frequency
50 or 60 Hz selectable
static variation
1.5%
dynamic variation
≤ 5% in 20 ms
Waveform
Sinusoidal
crest factor
3 : 1
BaTTeRies
charging time
4-6 hours
oveRload Times
100% < load < 110%
1 minute
110% < load < 150%
4 seconds
load > 150%
0.5 seconds
oTHeR feaTuRes
net weight (kg)
91
94
95
gross weight (kg)
99
102
103
dimensions (hwd) (mm)
2 x 660x175x455 / 2 x 4Ux19”x660
Packaging dimensions 
(hwd) (mm)
780 x 555 x (270+15)
smart active output
up to 98%
Protection devices
Overcurrent - short-circuit - overvoltage - undervoltage - thermal - low battery discharge protection
communication
USB / RS232 + slot for communications interface
input sockets
Terminal board
output socket
Terminal board + 2 IEC 320 C13
Regulations
EN 62040-1 EMC EN 62040-2 Directive 73/23 - 93/68 - 2004/108 EC EN 62040-3
ambient temperature
0°C / +40°C
Relative humidity
< 95% non-condensing
colour
Dark grey RAL 7016
noise level
< 45 dBA a 1 m
Two cable guides; terminal board connections; One IEC-16A plug; 
software; serial cable; keys to release mimic panel; handle kit