Riello Sentinel Dual (Low Power) 1500VA SDH1500 User Manual

Product codes
SDH1500
Page of 4
www.riello-ups.co.uk
UP
S
47
MODELS
SDH 1000
SDH 1500
SDH 2200
SDH 2200 ER
SDH 3000 
SDH 3000 ER
PoWeR
1000va/900W
1500va/1350W
2200va/1980W
2200va/1760W
3000va/2700W
3000va/2400W
inPuT
nominal voltage
220-230-240 Vac
voltage range without battery 
intervention
140 Vac < Vin < 276 Vac @50% LOAD / 184 Vac < Vin < 276 Vac @ 100% LOAD
max allowable voltage
300 V
nominal frequency
50 or 60 Hz ±5Hz
frequency range
50 Hz ± 5% / 60 Hz ± 5%
Power factor
> 0.98
current distortion
≤7%
By Pass
voltage tolerance
200 - 253 Vac
frequency tolerance
Frequency selected (from ±0.5Hz to ±5Hz configurable)
ouTPuT
voltage distortion with linear 
load / with non-linear load
< 2%
frequency
Selectable: 50 Hz or 60 Hz or automatic selection
static variation
± 1%
dynamic variation
≤ 5% in 20 msec.
Waveform
Sinusoidal
current crest factor
3 : 1
eco mode and 
smart active output
98%
BaTTeRies
Type
VRLA AGM lead acid maintenance free batteries
charging time
2-4 hours
oveRload Times
100% < load < 110%
1 minute
110% < load < 150%
4 seconds
load > 150%
0.5 seconds
oTHeR feaTuRes
net weight (kg)
17.5
18
30.5
15
31
15
gross weight (kg)
21
21.5
35
19.5
35.5
19.5
dimensions (hwd) (mm)
87x450x425 (2Ux19”x425)
87x450x625 (2Ux19”x625)
Packaging dimensions 
(hwd) (mm)
245x550x600
245x600x760
surge protection
300 joule
Protection devices
Overcurrent - short-circuit - overvoltage - undervoltage - thermal - low battery discharge protection
communication
USB / DB9 with RS232 and contacts / Slot for communications interface
input sockets
1 IEC 320 C14
1 IEC 320 C20
output socket
8 IEC 320 C13
8 IEC 320 C13 + 1 IEC 320 C19
compliance with standards
Safety: EN 62040-1 and Directive 2006/95/EL; EMC: EN 620040-2 category C2 and Directive 2004/108/EL
ambient temperature
0°C / +40°C
Relative humidity
< 95% non-condensing
colour
Black
noise level
< 40 dBA @ 1 m
standard equipment 
provided
Power cable, serial cable, USB cable, safety manual, quick start, software on CD-ROM