VEGA Americas Inc. PULS40 User Manual

Page of 88
86
VEGAPULS 42 and 44 – 4 … 20 mA
Setup
Continuation HART
® 
menu schematic VEGAPULS 42 and 44
1.3.4.8
available initialisation words:
..SOL
Meas. conditions solid
..LIQ
Meas. condition liquid
..FED
Delete false echo storage
..FEN04.58M
False echo, e.g. at 4.58 m create new
..FEN48.67FT
False echo, e.g. at 48.67 ft create new
..FEU03.68M
Extend false echo storage:
add a new false echo to the false echo storage at 3.68 m
..FEU36.05FT
add a new false echo to the false echo storage at 36.05 ft
initialisation word
(last entered)
Newly entered initialisation
word to be enquired with
ENTER and SEND
D
Note:
After entering the initialisation word, press "ENTER“ and then
"SEND“.
Confirm the message to change over to manual operation with
"OK“ and the message to switch over to automatic operation again
with "OK“.
Only then is the adjustment written into the sensor and made
active.
1.4.3.1
1.4.3.1.2
Low:
In case of failure current output
goes to 22 mA
High:
In case of failure current output
goes to < 3.6 mA
1.4.3.1.3
1.4.3.1.3.1
Warning:
Switch off
control!
False echo storage
Normally this menu is only
required for process vessels and
difficult installation conditions
of 1.3.4
of
1.4.3.
Generic: SENSOR
Message
..SOL
..FEN04.58M
  HELP     DEL    ESC
ENTER
Generic: SENSOR
Analog output
1 A01
13,467mA
2 A0 Alrm typ
3 Loop test
4 D/A trim
5 Scaled D/A trim
 HELP  SAVE HOME
Generic: SENSOR
Choose analog output
level
1 4  mA
2 20 mA
3 Other
4 End
         Abort
Enter
Generic: SENSOR
Fld dev output is
fixed at 4.000 mA
        ABORT
OK
Generic: SENSOR
A0 Alrm typ
Hold last out valu
 Exit