Read times from
Data carrier to
processor in
dynamic mode
(parametering:
2nd byte, bit 5 = 1,
without CRC-16 data
check)
Read times within the 1st block for dual read and compare:
The indicated times apply after the Data carrier has been recognized. If the Data carrier is not
yet recognized, an additional 45 ms for building the required energy field until the Data carrier is
recognized must be added.
Formula: t = (m + 1) * 0.5 ms
Example: Read 11 bytes starting at address 9, i.e. the highest address to be read is 19.
This corresponds to 10 ms.
Read/Write Times
m = highest address to be read
Data carrier with 64 byte blocks
No. of bytes
Read time [ms]
from 0 to 3
2
for each additional
byte add
0.5
from 0 to 63
29
S60_2-019_828318_0303-e mit CRC.p65
50
50
E
Function displays
on BIS S-60_2
The BIS S-60_2 uses the three side-mounted LED's to indicate important conditions of the
identification system.
LED
Status
Meaning
Ready /
red
Supply voltage OK; no hardware error,
Bus active
however, bus not active.
green
Supply voltage / hardware OK,
bus active.
CT1 present /
green
Data carrier read/write-ready at read/write head 1.
 operating
yellow
Read/write command at read/write head 1 in
process.
yellow flashes
Cable break to read/write head or not connected.
[f 
≈ 
2 Hz]
yellow flashes faster
Communication with R/W Head 1 is faulty
[f 
≈ 
4 Hz]
or R/W Head 1 is defective.
off
No data carrier in read/write range of
read/write head 1.
CT2 present /
green
Data carrier read/write-ready at read/write head 2.
operating
yellow
Read/write command at read/write head 2 in
process.
yellow flashes
Cable break to read/write head or not connected.
[f 
≈ 
2 Hz]
yellow flashes faster
Communication with R/W Head 2 is faulty
[f 
≈ 
4 Hz]
or R/W Head 2 is defective.
off
No data carrier in read/write range of
read/write head 2.
If all three LED's are synchronously flashing, it means a hardware error. Return the unit to the factory.
LED Display