Senstar Corporation LM100 User Manual

Page of 74
Senstar LM100 configuration overview
Page 48
Senstar LM100 Product Guide
segment - A segment can be made up of a single head or a contiguous group of heads 
(numerically sequential). Segments are software-defined during setup, and are assigned to 
zones for display and control purposes. Each Senstar LM100 system can be comprised of up 
to 50 segments. A single segment, or multiple segments, can be assigned to one zone. A 
segment can have a relay associated with it for alarm reporting. Each luminaire segment has 
an independent event threshold. Segments can also be defined as inactive (no alarm 
detection) by setting the threshold to the maximum value of 255.
zone - A zone is made up of one or more segments, and is used for the control and 
annunciation of sensor alarms (graphic map display with target location to the nearest head). 
There can be up to 50 alarm zones per Senstar LM100 system. Zones are defined in software 
to match the site-specific zone layout details (e.g., scheduled luminaire activation, CCTV 
coverage, fence sections, gates, buildings, etc.). Any grouping of segments can be assigned 
to a zone. The segments do not have to be contiguous, and can come from any combination 
of heads.
threshold - The threshold defines the received signal strength at which a fence disturbance is 
added to the Event Count for each head. When the received signal exceeds the threshold, the 
Event Count is incremented.
Senstar LM100 alarm detection
The luminaires provide the detection for the Senstar LM100 system by evaluating the minute 
vibrations from the fence to determine whether a disturbance is a valid intrusion or environmental 
activity. The characteristic signal response of a cut event is a sharp spike with a fast rising edge 
and fast falling edge. For a climb event, the response includes the fast rising edge caused by the 
initial contact with the fence, which is followed by a series of peaks and valleys resulting from the 
continued presence and changing stresses on the fence. Environmental activity is generally of 
longer duration, lower magnitude, and has more gradual increases and decreases. Each luminaire 
analyzes the fence disturbance signals from the section of fence it monitors to determine a valid 
alarm condition. The luminaires communicate over the wireless mesh network and pass the alarm 
data to the gateway via the luminaire AP. The gateway records and reports the alarm. The 
gateway can record and report multiple disturbances simultaneously for the full length of the 
protected fence.
The Threshold defines the signal strength for an Event (disturbance) to be added to the Event 
Count for each luminaire. An independent Threshold can be set for each defined luminaire 
segment communicating on the wireless network.
For each luminaire:
When the received signal exceeds the Threshold setting, the Event Count is incremented. 
The next Event will not be recorded until the period specified by the Event Window has lapsed.
Once the Event Window has lapsed, the next time the received signal exceeds the Threshold, 
the Event Count is incremented. 
The Event Count is incremented when the received signal remains above the Threshold for 
the period specified by the Event Window (i.e., a climbing intrusion). 
Each time the Event Count is incremented, the Alarm Window time is reset and begins 
counting down.
When the Event Count setting is reached within the Alarm Window time, a sensor alarm is 
triggered, and the Event Count is reset to zero.
If the Alarm Window Time lapses before the Event Count setting is reached, the Event Count 
is reset to zero without causing an alarm.