Rosemount Tank Radar AB 5900 User Manual
Reference Manual
300520EN, Rev AA
November 2009
Rosemount 5900 Series
6-8
Section 6. Service and Troubleshooting
6.2.5
Upgrading the Gauge Software
TankMaster WinSetup includes the option to upgrade Rosemount TankRadar
gauges with new application and boot software.
gauges with new application and boot software.
To upload a new program do the following:
1. Ensure that the 5900 level gauge has a stable communication with
TankMaster.
2. In the TankMaster WinSetup workspace window (Logical View) open the
Devices folder and select the 5900 level gauge to be upgraded (or select
the Devices folder to allow multiple devices programming).
the Devices folder to allow multiple devices programming).
3. Click the right mouse button and choose the Program option
(Program All option for multiple devices programming).
4. The 5900 will automatically appear in the Program These Devices pane
5. In case the Devices folder was selected for multiple programming,
5. In case the Devices folder was selected for multiple programming,
choose the 5900 gauge to be programmed from the Available Devices
pane and click the Move button.
pane and click the Move button.
6. Repeat for each device to be programmed.
Use the Remove button if you want to change the list of devices to be
programmed.
programmed.